Wiring with the display system
212
1SVC 440 795 M1100
Inputs
The function block inputs
>I1, >I2
and
>KP
can have
the following operands:
• Constants
• Markers MD, MW, MB
• Analog inputs IA01 to IA04
– IA01: Terminal I7
– IA02: Terminal I8
– IA03: Terminal I11
– IA04: Terminal I12
• Analog output QA01
• Actual value …QV> of another function block
Output
The function block output QV> can have the following
operands:
• Markers MD, MW, MB
• Analog output QA01
Value range for inputs and outputs
Example:
Value range
Resolution/unit
>I1
Input value of the function block
–32768 to +32767
>TG
Recovery time T
g
0 to 65535
in 100/ms
>KP
Proportional gain K
p
0 to 65535
in --/%
QV>
Output value
–32768 to +32767
Value at input
Value processed
in the function
block.
>TG
Recovery time T
g
250
25 s
>KP
Proportional gain K
p
1500
15