Make sure that …
The main circuit connections inside the drive cabinet correspond to the circuit diagrams.
The control unit has been connected. See the circuit diagrams.
Appropriate AC fuses and main disconnector have been installed.
There is an adequately sized protective earth (ground) conductor between the drive and the switchboard,
the conductor has been connected to appropriate terminal, and the terminal has been tightened to the
proper torque. Proper grounding has also been measured according to the regulations.
There is an adequately sized protective earth (ground) conductor between the energy storage and the
DC/DC converter, the conductor has been connected to appropriate terminal, and the terminal has
been tightened to the proper torque. Proper grounding has also been measured according to the regu-
lations.
The energy storage cable has been connected to the correct terminals of the DC/DC converter and
energy storage, and the terminals have been tightened to the proper torque.
The energy storage has been equipped with fuses for protecting energy storage cable in a cable short-
circuit situation.
The energy storage has been equipped with a disconnecting device.
The input power cable has been connected to the appropriate terminals, the phase order is right, and
the terminals have been tightened to the proper torque.
There is an adequately sized protective earth (ground) conductor between the motor and the drive,
and the conductor has been connected to appropriate terminal, and the terminal has been tightened
to the proper torque. (Pull on the conductors to check.). Proper grounding has also been measured
according to the regulations.
The motor cable has been connected to the appropriate terminals, the phase order is right, and the
terminals have been tightened to the proper torque.
The motor cable has been routed away from other cables.
No power factor compensation capacitors have been connected to the motor cable.
The control cables have been connected to the appropriate terminals, and the terminals have been
tightened to the proper torque.
If a drive bypass connection will be used: The direct-on-line contactor of the motor and the drive output
contactor are either mechanically and/or electrically interlocked, ie, cannot be closed simultaneously.
A thermal overload device must be used for protection when bypassing the drive. Refer to local codes
and regulations.
There are no tools, foreign objects or dust from drilling inside the drive.
Cover(s) of the motor connection box are in place. Cabinet shrouds are in place and doors are closed.
The motor and the driven equipment are ready for start.
The coolant connections between cubicles (if any) and to the cooling circuit are tight.
If the drive is equipped with a cooling unit: Refer to the cooling unit documentation for specific tasks.
74 Installation checklist of the drive
Summary of Contents for ACS880-1604LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 1604LC DC DC converter modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 16: ...16 ...
Page 34: ...34 ...
Page 42: ...Kits for ACS880 1604LC R8i unit in Rittal VX25 cabinets 42 Cabinet construction ...
Page 43: ...Stage 1 Installation of common parts Cabinet construction 43 10 ...
Page 45: ...Stage 3 Module installation parts Cabinet construction 45 10 ...
Page 46: ...Stage 4 DDC and energy storage connection 46 Cabinet construction ...
Page 47: ...Stage 5A DC connection with charging Cabinet construction 47 10 ...
Page 48: ...Stage 5B DC connection without charging 48 Cabinet construction ...
Page 49: ...Stage 6 Cooling components Cabinet construction 49 10 ...
Page 50: ...Stage 7 DDC module and filter installation 50 Cabinet construction ...
Page 51: ...Stage 8 Swing frame and shroud installation Cabinet construction 51 10 ...
Page 58: ...58 ...
Page 72: ...72 ...
Page 124: ...124 ...
Page 138: ...138 ...
Page 148: ...148 ...
Page 150: ...R8i DC DC converter module 150 Dimension drawings ...
Page 151: ...BDCL filter module Dimension drawings 151 ...
Page 152: ...Quick connector 152 Dimension drawings ...
Page 153: ...BCU control unit Dimension drawings 153 ...
Page 154: ...BAMU voltage current measurement unit Dimensions in mm 1 mm 0 0394 in 154 Dimension drawings ...