Implementing an interlocking between the disconnecting devices
The customer (or the system integrator) must implement an interlocking circuit between the
DC switch/disconnector of the DC/DC converter unit and the energy storage disconnector.
The user must not be able to close the energy storage disconnector before closing the DC
switch/disconnector [Q11] of the DC/DC converter.
Selecting and routing the energy storage cables
■
Recommended cables
The customer (or the system integrator) must acquire and connect the energy storage
cables. It is possible to use either 3-conductor shielded cable(s) or 4-conductor shielded
cables:
•
If you use a 4-conductor shielded cable, use 2 conductors for plus and 2 conductors
for minus and the shield for PE.
•
If you use a 3-conductor shielded cable, use 1 conductor for plus, 1 conductor for minus
and 1 conductor and the shield for PE.
■
Typical cable sizes
See the technical data.
■
Minimizing electromagnetic interference
The customer (or the system integrator) must obey these rules in order to minimize the
electromagnetic interference caused by rapid current changes in the energy storage cables:
•
Shield the energy storage cabling completely, either by using shielded cable or a metallic
enclosure. Unshielded single-core cable can only be used if it is routed inside a cabinet
that efficiently suppresses radiated emissions.
•
Install the cables away from other cable routes.
•
Avoid long parallel runs with other cables. The minimum parallel cabling separation
distance should be 0.3 meters.
•
Cross other cables at right angles.
Keep the cable as short as possible in order to minimize the radiated emissions and stress
on converter IGBT semiconductors. The longer the cable, the higher the radiated emissions,
inductive load and voltage peaks over the IGBTs of the DC/DC converter.
■
Maximum cable length
The maximum cable length of the energy storage cable(s) is 100 m (328 ft).
56 Guidelines for planning electrical installation
Summary of Contents for ACS880-1604LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 1604LC DC DC converter modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 16: ...16 ...
Page 34: ...34 ...
Page 42: ...Kits for ACS880 1604LC R8i unit in Rittal VX25 cabinets 42 Cabinet construction ...
Page 43: ...Stage 1 Installation of common parts Cabinet construction 43 10 ...
Page 45: ...Stage 3 Module installation parts Cabinet construction 45 10 ...
Page 46: ...Stage 4 DDC and energy storage connection 46 Cabinet construction ...
Page 47: ...Stage 5A DC connection with charging Cabinet construction 47 10 ...
Page 48: ...Stage 5B DC connection without charging 48 Cabinet construction ...
Page 49: ...Stage 6 Cooling components Cabinet construction 49 10 ...
Page 50: ...Stage 7 DDC module and filter installation 50 Cabinet construction ...
Page 51: ...Stage 8 Swing frame and shroud installation Cabinet construction 51 10 ...
Page 58: ...58 ...
Page 72: ...72 ...
Page 124: ...124 ...
Page 138: ...138 ...
Page 148: ...148 ...
Page 150: ...R8i DC DC converter module 150 Dimension drawings ...
Page 151: ...BDCL filter module Dimension drawings 151 ...
Page 152: ...Quick connector 152 Dimension drawings ...
Page 153: ...BCU control unit Dimension drawings 153 ...
Page 154: ...BAMU voltage current measurement unit Dimensions in mm 1 mm 0 0394 in 154 Dimension drawings ...