Converter unit control devices
■
DC switch/disconnector
You can equip the DC/DC converter cabinet with DC switch/disconnector [Q11]. A converter
unit with a DC switch/disconnector must also have a precharge circuit including a charging
switch.
The DC switch/disconnector allows the isolation of the unit from the DC bus. Before the unit
is reconnected to the DC bus, you must charge the capacitors of the converter modules
through a charging circuit.
WARNING!
You must also switch off the charging switch to disconnect the DC/DC converter
from the DC supply. Do not operate the DC switch/disconnector under load.
■
Charging switch
If the converter is equipped with a DC switch/disconnector, you must equip the converter
unit with a charging circuit including a charging switch [Q10]. If you have connected the
switches as shown in the example circuit diagrams, close the charging switch first when the
converter unit is connected to an energized DC bus. When the charging is finished, close
the main DC switch/disconnector and open the charging switch. (The converter unit will not
start if the charging switch is closed.)
WARNING!
You must also switch off the charging switch to disconnect the DC/DC converter
from the DC supply.
■
Door lights
You can install the load disconnected indicator on the cabinet door. This indicator shows
the state of the energy storage disconnecting device.
You can install also the charging OK indicator and DC/DC converter disconnected indicator,
if the DC switch/disconnector is equipped.
■
BCU control unit
The DC/DC converter module is controlled by a BCU control unit. For more information, see
.
■
ACX-AP-x control panel
The ACX-AP-x control panel is the user interface of the unit. With the control panel, you
can:
•
start and stop the unit
•
view and reset the fault and warning messages, and view the fault history
•
view actual signals
•
change parameter settings
•
change between local and external control.
To be able to start and stop the unit by the control panel, you must have the
parameter-defined Run enable signal and Start enable signal on (1). The control panel must
also be in local control mode.
28 Operation principle and hardware description
Summary of Contents for ACS880-1604LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 1604LC DC DC converter modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 16: ...16 ...
Page 34: ...34 ...
Page 42: ...Kits for ACS880 1604LC R8i unit in Rittal VX25 cabinets 42 Cabinet construction ...
Page 43: ...Stage 1 Installation of common parts Cabinet construction 43 10 ...
Page 45: ...Stage 3 Module installation parts Cabinet construction 45 10 ...
Page 46: ...Stage 4 DDC and energy storage connection 46 Cabinet construction ...
Page 47: ...Stage 5A DC connection with charging Cabinet construction 47 10 ...
Page 48: ...Stage 5B DC connection without charging 48 Cabinet construction ...
Page 49: ...Stage 6 Cooling components Cabinet construction 49 10 ...
Page 50: ...Stage 7 DDC module and filter installation 50 Cabinet construction ...
Page 51: ...Stage 8 Swing frame and shroud installation Cabinet construction 51 10 ...
Page 58: ...58 ...
Page 72: ...72 ...
Page 124: ...124 ...
Page 138: ...138 ...
Page 148: ...148 ...
Page 150: ...R8i DC DC converter module 150 Dimension drawings ...
Page 151: ...BDCL filter module Dimension drawings 151 ...
Page 152: ...Quick connector 152 Dimension drawings ...
Page 153: ...BCU control unit Dimension drawings 153 ...
Page 154: ...BAMU voltage current measurement unit Dimensions in mm 1 mm 0 0394 in 154 Dimension drawings ...