Notes:
1)
Default use of the signal in the control program. The use can be changed by a parameter.
See also the delivery-specific circuit diagrams.
2)
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [0(2)…10 V,
R
in
> 200 kohm] input
selected by switch AI1. Change of setting requires reboot of control unit.
3)
Current [0(4)…20 mA,
R
in
= 100 ohm] or voltage [0(2)…10 V,
R
in
> 200 kohm] input
selected by switch AI2. Change of setting requires reboot of control unit.
4)
Total load capacity of these outputs is 4.8 W (200 mA at 24 V) minus the power taken by
DIO1 and DIO2.
5)
Determines whether DICOM is separated from DIOGND (ie, common reference for digital
inputs floats).
DICOM=DIOGND
ON: DICOM connected to DIOGND. OFF: DICOM and DIOGND separate.
6)
This input only acts as a true Safe torque off input in inverter control units. In other
applications (such as a supply or brake unit), de-energizing the IN1 and/or IN2 terminal will
stop the unit but not constitute a true safety function.
External power supply for the control unit (XPOW)
The control unit is powered from a 24 V DC, 2 A supply through terminal block XPOW. With
a type BCU control unit, a second supply can be connected to the same terminal block for
redundancy.
The XD2D connector
The XD2D connector provides an RS-485 connection that can be used for
•
basic master/follower communication with one master drive and multiple followers,
•
fieldbus control through the embedded fieldbus interface (EFB), or
•
drive-to-drive (D2D) communication implemented by application programming (not
supported by the DC/DC converter control program).
See the firmware manual of the drive for the related parameter settings.
Enable bus termination on the units at the ends of the drive-to-drive link. Disable bus
termination on the intermediate units.
Use shielded twisted-pair cable with a twisted pair for data and a wire or another pair for
signal ground (nominal impedance 100 to 165 ohm, for example Belden 9842) for the wiring.
For best immunity, ABB recommends high quality cable. Keep the cable as short as possible.
Avoid unnecessary loops and parallel runs near power cables such as motor cables.
The following diagram shows the wiring between control units.
Control units of the drive 143
Summary of Contents for ACS880-1604LC
Page 1: ... ABB INDUSTRIAL DRIVES ACS880 1604LC DC DC converter modules Hardware manual ...
Page 2: ......
Page 4: ......
Page 12: ...12 ...
Page 16: ...16 ...
Page 34: ...34 ...
Page 42: ...Kits for ACS880 1604LC R8i unit in Rittal VX25 cabinets 42 Cabinet construction ...
Page 43: ...Stage 1 Installation of common parts Cabinet construction 43 10 ...
Page 45: ...Stage 3 Module installation parts Cabinet construction 45 10 ...
Page 46: ...Stage 4 DDC and energy storage connection 46 Cabinet construction ...
Page 47: ...Stage 5A DC connection with charging Cabinet construction 47 10 ...
Page 48: ...Stage 5B DC connection without charging 48 Cabinet construction ...
Page 49: ...Stage 6 Cooling components Cabinet construction 49 10 ...
Page 50: ...Stage 7 DDC module and filter installation 50 Cabinet construction ...
Page 51: ...Stage 8 Swing frame and shroud installation Cabinet construction 51 10 ...
Page 58: ...58 ...
Page 72: ...72 ...
Page 124: ...124 ...
Page 138: ...138 ...
Page 148: ...148 ...
Page 150: ...R8i DC DC converter module 150 Dimension drawings ...
Page 151: ...BDCL filter module Dimension drawings 151 ...
Page 152: ...Quick connector 152 Dimension drawings ...
Page 153: ...BCU control unit Dimension drawings 153 ...
Page 154: ...BAMU voltage current measurement unit Dimensions in mm 1 mm 0 0394 in 154 Dimension drawings ...