![ABB ACS 6000 Service And Maintenance Manual Download Page 75](http://html1.mh-extra.com/html/abb/acs-6000/acs-6000_service-and-maintenance-manual_3488110075.webp)
ABB
ACS 6000 Maintenance Manual
3BHS202077 ZAB E01 Rev. C
11-1 (6)
Chapter 11 - Changing IGCTs in DIU
The tools listed below are part of the tool set (ident. no. 3BHS130246)
delivered with the ACS 6000.
•
1/2 " reversible ratchet
•
24 mm socket
•
10 mm socket
•
Cable ties
Before starting any work on the DIU do the following:
1
Deenergize and ground the ACS 6000.
Danger: The ACS 6000 is a high voltage device.
Make sure that the cabinet has been completely deenergized and that
power cannot be applied by accident.
Failure to do so may result in injury or death.
Note: After switching off the mains and after the motor has come to a stop,
allow the DC link capacitors to discharge. The light GND.- SWITCH
UNLOCKED must be on before grounding the ACS 6000.
2
Switch off the auxiliary power supply. Refer to the wiring diagrams to
identify the circuit breaker.
11.1
Required Tools and Accessories
11.2
Safety