Chapter 7 – Fault Tracing
ACA 635 IGBT Supply Sections
7-3
EARTH FAULT
Par. 9.12 bit 13
Earthed/Grounded Network
The sum of line currents measured with
internal current transducers is too high.
Earth fault in AC filter, line converter, DC link,
inverter(s), motor cables or motor, or current
unbalance in parallel connected converters.
Check motors.
Check motor cables.
Check the ISU fuses (parallel connected
units).
Check the ISU.
Check inverter(s).
Check AC filter.
NET LOST
Par. 9.12 bit 10
Network voltage is lost during modulation. Line
current is below 0.0064
×
I
1base (10s/60s)
. The
situation may cause DC link undervoltage.
Check network conditions.
PANEL LOST
Par. 9.12 bit 1
A Local Control device (CDP 312 or
Drive
Window)
has ceased communicating.
This can be caused by the disconnection of the
selected local control device during local
control or an internal fault in the local
controlling device. This warning transfers the
ISU to remote mode.
Check Control Panel connector. Replace
Control Panel in the mounting platform.
NO COMMUNICATION
(x)
This message is generated by the Control
Panel CDP 312 control program.
There is a cabling problem or a hardware
malfunction on the Panel Link.
(4) = Panel type is not compatible with the
version of the converter application program.
Check the Panel Link connections.
Press the RESET key. The panel reset may
take up to half a minute, please wait.
Check the Panel type and the version of the
drive application program. The Panel type is
printed on the cover of the Panel.
ID N CHANGED
The ID number of the ISU has been changed
from 1 (the change is not displayed on the
Control Panel CDP 312).
To change the ID number back to 1 go to Drive
Selection Mode by pressing
DRIVE
. Press
ENTER
. Set the ID number to 1. Press
ENTER.
LOAD FACTORY
Factory parameter settings are being restored. Please wait.
Fault Messages
Fault Text
Cause
What to do
ACS 600 TEMP
Par. 9.01 bit 3
Par. 9.11 bit 3
The ACS 600 internal temperature is
excessive. The trip level of the converter
module temperature is 125
°
C.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check line current against unit current.
AMBIENT TEMP
Par. 9.02 bit 7
I/O control board temperature is lower than
+5
°
C or e73
°
C.
Check ambient temperature in the auxiliary
control unit (ACU).
CHARGING FLT
Par. 9.11 bit 0
DC link voltage is not high enough after
charging procedure.
DC link voltage has not exceeded the value of
Par. 30.12 DC UNDERVOLT TRIP or current is
not below 5% of
I
1base (10s/60s)
at the end of the
charging.
Check charging circuit fuses.
Check charging circuit.
Check possible short-circuit in DC link.
Check the setting of Par. 30.12 DC
UNDERVOLT TRIP.
Faulty PPCC link (DC voltage measurement is
zero).
Check the PPCC link. See fault message
PPCC LINK.
Warning Messages
Warning
Cause
What to do
Summary of Contents for ACS 600 MultiDrive
Page 4: ......
Page 8: ...Safety Instructions vi ACA 635 IGBT Supply Sections ...
Page 57: ...Chapter 7 Fault Tracing 7 8 ACA 635 IGBT Supply Sections ...
Page 99: ...Appendix B Circuit Diagrams B 2 ACA 635 IGBT Supply Sections H ...
Page 100: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 3 ...
Page 101: ...Appendix B Circuit Diagrams B 4 ACA 635 IGBT Supply Sections ...
Page 102: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 5 ...
Page 103: ...Appendix B Circuit Diagrams B 6 ACA 635 IGBT Supply Sections ...
Page 104: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 7 ...
Page 105: ...Appendix B Circuit Diagrams B 8 ACA 635 IGBT Supply Sections ...
Page 106: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 9 ...
Page 107: ...Appendix B Circuit Diagrams B 10 ACA 635 IGBT Supply Sections ...
Page 108: ......