Chapter 6 – Firmware Description
6-6
ACA 635 IGBT Supply Sections
The synchronization parameters are listed below.
Starting Sequence
During the charging procedure the main contactor is closed, and after
the synchronization routine is completed, the modulator is started and
the ISU runs normally.
A simplified block diagram of the modulator starting (from starting
switch on the cabinet door or via fieldbus) is presented below. For
description of the starting procedure see the next pages.
Code
Parameter Unit
Description
140.10 ZERO VECT LENGTH 200
m
s Length of the short-circuit pulse
140.11 PHASE LOSS LIMIT
A
Current limit for short-circuit current
99.06
FAST SYNC
One short-circuit pulse is used
Fault
9.02
SUPPLY PHASE
Synchronization failed, phase(s)
missing
9.11
SYNCHRO FLT
Synchronization failed, short-circuit
current below limit
&
7.01
MAIN CTRL WORD
bit 0
DI2
SWITCH
enable (1) = I/O
&
(1)
(0)
7.01
MAIN CTRL WORD
bit 3
(0)
(1)
(1)
(0)
98.01
COMMAND SEL
> 1
8.01
MAIN STATUS WORD
bit 8
Summary of Contents for ACS 600 MultiDrive
Page 4: ......
Page 8: ...Safety Instructions vi ACA 635 IGBT Supply Sections ...
Page 57: ...Chapter 7 Fault Tracing 7 8 ACA 635 IGBT Supply Sections ...
Page 99: ...Appendix B Circuit Diagrams B 2 ACA 635 IGBT Supply Sections H ...
Page 100: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 3 ...
Page 101: ...Appendix B Circuit Diagrams B 4 ACA 635 IGBT Supply Sections ...
Page 102: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 5 ...
Page 103: ...Appendix B Circuit Diagrams B 6 ACA 635 IGBT Supply Sections ...
Page 104: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 7 ...
Page 105: ...Appendix B Circuit Diagrams B 8 ACA 635 IGBT Supply Sections ...
Page 106: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 9 ...
Page 107: ...Appendix B Circuit Diagrams B 10 ACA 635 IGBT Supply Sections ...
Page 108: ......