Chapter 8 – Parameters
8-18
ACA 635 IGBT Supply Sections
23 DC Bus Reference
With the help of the Parameter 23.01 DC VOLT REF, the DC link
voltage can be raised higher than with a conventional 6-pulse diode
rectifier in order to compensate a low voltage level in the network.
Note:
Check the motor insulation requirement. See
ACS 600 MultiDrive Safety and Product Information
guide, EN code
63982229, or ACS/ACC 6x7 Hardware Manual, EN code 61329005.
Example
If the line voltage is 380 V, fully loaded DC voltage with 6-pulse diode
rectifier is 1.35
×
380 V = 513 V. If the desired motor rms level is 400 V
with sinusoidal voltage (peak value =
Ö
2
×
400 V = 565 V), the voltage
drop can be compensated simply by setting Parameter 23.01 DC
VOLT REF to value 565. However, the input current to produce the
output power is still calculated on the basis of 380 V: P =
Ö
3
×
380
×
line
current.
24 Reactive Power
Code
Parameter
T
y
p
e
Range
Description
Integer
Scaling
23
DC VOLT REF
23.01
DC VOLT REF
R See table below.
User-given setpoint value for intermediate circuit DC voltage
reference
1 = 1 V
Code Parameter
T
y
p
e
Default
Range
Description
Integer
Scaling
24
REACTIVE
POWER
24.01
Q POWER REF
R
0%
-100%...+100%
Setpoint value for reactive power control in
percentage of Par. 4.06 CONV NOM POWER.
Reactive power control is capable of generating
the set amount of reactive power to the network
(positive = capacitive, negative = reactive).
1 = 1 %
Par. 4.04 CONV NOM
VOLTAGE
(V)
Range of Par. 23.01:
(65% ...120%)
×
Ö
2
×
Par. 4.04 CONV
NOM VOLTAGE
Minimum (V)
Maximum (V)
415
380
706
500
457
851
690
632
1174
Summary of Contents for ACS 600 MultiDrive
Page 4: ......
Page 8: ...Safety Instructions vi ACA 635 IGBT Supply Sections ...
Page 57: ...Chapter 7 Fault Tracing 7 8 ACA 635 IGBT Supply Sections ...
Page 99: ...Appendix B Circuit Diagrams B 2 ACA 635 IGBT Supply Sections H ...
Page 100: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 3 ...
Page 101: ...Appendix B Circuit Diagrams B 4 ACA 635 IGBT Supply Sections ...
Page 102: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 5 ...
Page 103: ...Appendix B Circuit Diagrams B 6 ACA 635 IGBT Supply Sections ...
Page 104: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 7 ...
Page 105: ...Appendix B Circuit Diagrams B 8 ACA 635 IGBT Supply Sections ...
Page 106: ...Appendix B Circuit Diagrams ACA 635 IGBT Supply Sections B 9 ...
Page 107: ...Appendix B Circuit Diagrams B 10 ACA 635 IGBT Supply Sections ...
Page 108: ......