Parameter listing and descriptions
299
ACH550-01 User's Manual
5307
EFB CRC ERRORS
0…65535
Contains a count of the messages with a CRC error received by the
drive. For high counts, check:
• Ambient electro-magnetic noise levels – high noise levels generate
errors.
• CRC calculations for possible errors.
5308
EFB UART ERRORS
0…65535
Contains a count of the messages with a character error received by the
drive.
5309
EFB STATUS
0…7
Contains the status of the EFB protocol.
0 =
IDLE
– EFB protocol is configured, but not receiving any messages.
1 =
EXECUT
INIT
– EFB protocol is initializing.
2 =
TIME
OUT
– A time-out has occurred in the communication between
the network master and the EFB protocol.
3 =
CONFIG
ERROR
– EFB protocol has a configuration error.
4 =
OFF
-
LINE
– EFB protocol is receiving messages that are NOT
addressed to this drive.
5 =
ON
-
LINE
– EFB protocol is receiving messages that are addressed to
this drive.
6 =
RESET
– EFB protocol is performing a hardware reset.
7 =
LISTEN
ONLY
– EFB protocol is in listen-only mode.
5310
EFB PAR 10
0…65535
Protocol specific. See manuals
Embedded Fieldbus (EFB) Control
(3AFE68320658 [English]) and
BACnet® Protocol
(3AUA0000004591
[English])
5311
EFB PAR 11
0…65535
See parameter 5310.
5312
EFB PAR 12
0…65535
See parameter 5310.
5313
EFB PAR 13
0…65535
See parameter 5310.
5314
EFB PAR 14
0…65535
See parameter 5310.
5315
EFB PAR 15
0…65535
See parameter 5310.
5316
EFB PAR 16
0…65535
See parameter 5310.
5317
EFB PAR 17
0…65535
See parameter 5310.
5318
EFB PAR 18
0…65535
See parameter 5310.
Code Description
Range
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com