Parameter listing and descriptions
295
ACH550-01 User's Manual
5131
FBA STATUS
0…6
Contains the status of the adapter module.
0 =
IDLE
– Adapter not configured.
1 =
EXECUT
INIT
– Adapter is initializing.
2 =
TIME
OUT
– A time-out has occurred in the communication between
the adapter and the drive.
3 =
CONFIG
ERROR
– Adapter configuration error.
• The major or minor revision code of the adapter’s CPI firmware
revision differs from that stated in the drive’s configuration file.
4 =
OFF
-
LINE
– Adapter is off-line.
5 =
ON
-
LINE
– Adapter is on-line.
6 =
RESET
– Adapter is performing a hardware reset.
5132
FBA CPI FW REV
0…0xFFFF
Contains the revision of the module’s CPI program. Format is xyz,
where:
• x = major revision number
• y = minor revision number
• z = correction number.
Example:
107 = revision 1.07
5133
FBA APPL FW REV
0…0xFFFF
Contains the revision of the module’s application program. Format is
xyz, where:
• x = major revision number
• y = minor revision number
• z = correction number.
Example:
107 = revision 1.07
Code Description
Range