ACH550-01 User's Manual
Application macros and wiring 125
Connection for obtaining 0…10 V from analogue
outputs
To obtain 0…10 V from analogue outputs, connect a 500 ohm
resistor (or two 1 kohm resistors in parallel) between the
analogue output and analogue output circuit common AGND.
Examples for analogue output 2 AO2 are shown in the figure
below.
X1
8
AO2
Analogue output 2. Default output
0…20 mA.
9
AGND
Analogue input circuit common. Internally
connected to chassis through a 1 Mohm
resistor.
500 ohm
X1
8
AO2
Analogue output 2. Default output
0…20 mA.
9
AGND
Analogue input circuit common. Internally
connected to chassis through a 1 Mohm
resistor.
1 kohm
1 kohm
0…10
V
0…1
0
V
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com