244
Parameter listing and descriptions
ACH550-01 User's Manual
Group 30: FAULT FUNCTIONS
This group defines situations that the drive should recognise as
potential faults and how the drive should respond if the fault is
detected.
Code Description
Range
3001
AI<MIN FUNCTION
0…3
Defines the drive response if the analogue input (
AI
) signal drops below
the fault limits and
AI
is used:
• as the active reference source (
Group 11: REFERENCE SELECT
)
• as the Process or External PID controllers' feedback or setpoint
source (
Group 40: PROCESS PID SET 1
,
Group 41: PROCESS PID
SET 2
or
Group 42: EXT / TRIM PID
) and the corresponding PID
controller is active.
3021
AI
1
FAULT
LIMIT
and 3022
AI
2
FAULT
LIMIT
set the minimum limits.
0 =
NOT
SEL
– No response.
1 =
FAULT
– Displays a fault (7,
AI
1
LOSS
or 8,
AI
2
LOSS
) and the drive
coasts to stop.
2 =
CONST
SP
7 – Displays an alarm (2006,
AI
1
LOSS
or 2007,
AI
2
LOSS
)
and sets the speed using 1208
CONST
SPEED
7.
3 =
LAST
SPEED
– Displays an alarm (2006,
AI
1
LOSS
or 2007,
AI
2
LOSS
)
and sets the speed using the last operating level. This value is the
average speed over the last 10 seconds.
WARNING!
If you select
CONST
SP
7 or
LAST
SPEED
, make sure that
continued operation is safe when the analogue input signal is lost.
3002
PANEL COMM ERR
1…3
Defines the drive response to a control panel (operator keypad)
communication error.
1 =
FAULT
– Displays a fault (10,
PANEL
LOSS
) and the drive coasts to
stop.
2 =
CONST
SP
7 – Displays an alarm (2008,
PANEL
LOSS
) and sets the
speed using 1208
CONST
SPEED
7.
3 =
LAST
SPEED
– Displays an alarm (2008,
PANEL
LOSS
) and sets the
speed using the last operating level. This value is the average speed
over the last 10 seconds.
WARNING!
If you select
CONST
SP
7 or
LAST
SPEED
, make sure that
continued operation is safe when the control panel communication
is lost.