230
Parameter listing and descriptions
ACH550-01 User's Manual
2209
RAMP INPUT 0
-6…7
Defines control for forcing the speed to 0 with the currently used
deceleration ramp (see parameters 2203
DECELER
TIME
1 and 2206
DECELER
TIME
2).
0 =
NOT
SEL
– Not selected.
1 =
DI
1 – Defines digital input
DI
1 as the control for forcing the speed
to 0.
• Activating the digital input forces the speed to 0, after which the
speed will stay at 0.
• De-activating the digital input: speed control resumes normal
operation.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for forcing
the speed to 0.
• See
DI
1 above.
7 =
COMM
– Defines bit 13 of the Command Word 1 as the control for
forcing the speed to 0.
•The command word is supplied through fieldbus communication.
• The Command Word is parameter 0301.
-1 =
DI
1(
INV
) – Defines inverted digital input
DI
1 as the control for forcing
the speed to 0.
• De-activating the digital input forces the speed to 0.
• Activating the digital input: speed control resumes normal operation.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6
as the control for forcing the speed to 0.
• See
DI
1(
INV
) above.
Code Description
Range