Parameter listing and descriptions
211
ACH550-01 User's Manual
1605
USER PAR SET CHG
-6…6
Defines control for changing the User Parameter Set.
• See parameter 9902
APPLIC
MACRO
.
• The drive must be stopped to change User Parameter Sets.
• During a change, the drive will not start.
Note:
Always save the User Parameter Set after changing any
parameter settings or performing a motor identification.
• Whenever the power is cycled, or parameter 9902
APPLIC
MACRO
is
changed, the drive loads the last settings saved. Any unsaved
changes to a user parameter set are lost.
Note:
The value of this parameter (1605) is not included in the User
Parameter Sets, and it does not change if User Parameter Sets change.
Note:
You can use a relay output to supervise the selection of User
Parameter Set 2.
• See parameter 1401.
0 =
NOT
SEL
– Defines the control panel (operator keypad) as the only
control for changing User Parameter Sets (using parameter 9902).
1 =
DI
1 – Defines digital input
DI
1 as a control for changing User
Parameter Sets.
• The drive loads User Parameter Set 1 on the falling edge of the
digital input.
• The drive loads User Parameter Set 2 on the rising edge of the
digital input.
• The User Parameter Set changes only when the drive is stopped.
2…6 =
DI
2…
DI
6 – Defines digital input
DI
2…
DI
6 as the control for
changing User Parameter Sets.
• See
DI
1 above.
-1 =
DI
1(
INV
) – Defines an inverted digital input
DI
1 as a control for
changing User Parameter Sets.
• The drive loads User Parameter Set 1 on the rising edge of the
digital input.
• The drive loads User Parameter Set 2 on the falling edge of the
digital input.
• The User Parameter Set changes only when the drive is stopped.
-2…-6 =
DI
2(
INV
)…
DI
6(
INV
) – Defines an inverted digital input
DI
2…
DI
6
as a control for changing User Parameter Sets.
• See
DI
1(
INV
) above.