Real-time clock and timed functions
133
ACH550-01 User's Manual
4. Connecting parameters
The parameter example 1201
CONST
SPEED
SEL
has to be
connected to the timer so that the timer acts as the source of
constant speed activating. A parameter can only be connected
to one timer.
To connect the parameter, follow these steps:
6
Press SAVE to save the
new value.
7
The new value is displayed
below the TIMER 1 SRC
text. Press EXIT to return to
the main menu.
1
Press MENU to go to the
main menu.
2
Select PARAMETERS with
the UP/DOWN keys. Then
press ENTER to go to the
Parameters mode.
3
Scroll to group 12
CONSTANT SPEEDS and
press SEL.
4
Scroll to parameter 1201
CONSTANT SPEED SEL
and press EDIT.
3626 TIMER 1 SRC
PAR EDIT
P1
[1]
OFF
CANCEL
SAVE
00:00
3622 BOOST SEL
3623 BOOST TIME
3626 TIMER 1 SRC
P1
3627 TIMER 2 SRC
PARAMETERS
EXIT
EDIT
00:00
OFF
0 A
0 Hz
0 %
0.
0.
0.
0.0Hz
OFF
MENU
00:00
PARAMETERS
ASSISTANTS
CHANGED PAR
EXIT
ENTER
00:00
1
OFF
MAIN MENU
03 FB ACTUAL SIGNALS
04 FAULT HISTORY
10 START/STOP/DIR
11 REFERENCE SELECT
12 CONSTANT SPEEDS
PAR BACKUP
12
EXIT
SEL
00:00
OFF
1201 CONST SPEED SEL
DI3
1202 CONST SPEED 1
1203 CONST SPEED 2
1204 CONST SPEED 3
PARAMETERS
EXIT
EDIT
00:00
OFF