Name of input
Type
Default
Description
Value when
activated
Value when
deactivated
IN14
BOOLEAN
0
Input 14
8192
0
IN15
BOOLEAN
0
Input 15
16384
0
IN16
BOOLEAN
0
Input 16
32768
0
The sum of the numbers in column “Value when activated” when all INx (where
1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can
be converted to an integer by the IB16 function block.
9.11
Integer to Boolean 16 conversion with logic node
representation ITBGAPC
SEMOD158419-1 v3
9.11.1
Identification
SEMOD167944-2 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion with
logic node representation
ITBGAPC
-
-
9.11.2
Application
SEMOD158512-5 v7
Integer to boolean 16 conversion with logic node representation function
(ITBGAPC) is used to transform an integer into a set of 16 boolean signals.
ITBGAPC function can receive an integer from a station computer – for example,
over IEC 61850–8–1. This function is very useful when the user wants to generate
logical commands (for selector switches or voltage controllers) by inputting an
integer number. ITBGAPC function has a logical node mapping in IEC 61850.
The Integer to Boolean 16 conversion with logic node representation function
(ITBGAPC) will transfer an integer with a value between 0 to 65535
communicated via IEC 61850 and connected to the ITBGAPC function block to a
combination of activated outputs OUTx where 1≤x≤16.
The values of the different OUTx are according to the Table
.
If the BLOCK input is activated, it freezes the logical outputs at the last value.
1MRK 511 423-UEN A
Section 9
Logic
Bay control REC650 2.2 IEC
187