15.12.2.2
Synchronization
M11348-143 v4
The setting parameters for the real-time clock with external time synchronization
are set via local HMI or PCM600. The path for Time Synchronization parameters
on local HMI is
Main menu/Configuration/Time/Synchronization
. The
parameters are categorized as Time Synchronization (TIMESYNCHGEN) and
IRIG-B settings (IRIG-B:1) in case that IRIG-B is used as the external time
synchronization source.
TimeSynch
M11348-167 v15
When the source of the time synchronization is selected on the local HMI, the
parameter is called
TimeSynch
. The time synchronization source can also be set
from PCM600. The setting alternatives are:
FineSyncSource
which can have the following values:
•
Off
•
SPA
•
LON
•
BIN
(Binary Minute Pulse)
•
SNTP
•
IRIG-B
•
PPS
CoarseSyncSrc
which can have the following values:
•
Off
•
SPA
•
LON
•
DNP
•
IEC 60870-5-103
The function input to be used for minute-pulse synchronization is called
BININPUT. For a description of the BININPUT settings, see the
Technical
Manual
.
The system time can be set manually, either via the local HMI or via any of the
communication ports. The time synchronization fine tunes the clock (seconds and
milliseconds).
The parameter
SyncMaster
defines if the IED is a master, or not a master for time
synchronization within a Substation Automation System, for IEDs connected in a
communication network (IEC 61850-8-1). The
SyncMaster
can have the following
values:
•
Off
•
SNTP -Server
Section 15
1MRK 511 423-UEN A
Basic IED functions
286
Bay control REC650 2.2 IEC
Application manual