BLOCK
BLKLKOUT
TRIN
TRINL1
TRINL2
TRINL3
PSL1
PSL2
PSL3
1PTRZ
1PTREF
P3PTR
SETLKOUT
RSTLKOUT
STDIR
TRIP
SMPPTRC
TRL1
TRL2
TRL3
TR1P
TR2P
TR3P
CLLKOUT
START
STL1
STL2
STL3
FW
REV
Phase segregated trip L1, L2 and L3
from example line differential or
distance protection
Phase selection L1, L2 and L3 from
external phase selection logic
Trip by communication scheme of
distance protection if required to
provide a single pole trip
Trip by communication scheme of
earth fault protection if required to
provide single pole trip
To activate lockout for any trip
To reset lockout
Protection functions with 3
phase trip, for example time
delayed overcurrent protection
OR
To prepare 3 phase trip
for any trip signal
SMBRREC
PREP3P
TR3P
STN
IEC05000545-5-en.vsdx
IEC05000545 V5 EN-US
Figure 91:
The trip logic function SMPPTRC used for single-phase tripping
application
9.1.2.3
Single-, two- or three-phase tripping
M14828-15 v5
The single-/two-/three-phase tripping mode provides single-phase tripping for
single-phase faults, two-phase tripping for two-phase faults and three-phase
tripping for three-phase faults. The operating mode is always used together with an
autoreclosing scheme with setting
ARMode
=
1/2/3 ph
or
ARMode
=
1/2 ph
.
The functionality is very similar to the single-phase scheme described above.
However, in addition to the connections for single phase SMBRREC must also be
informed that the trip is two phases by connecting the output TR2P to the input
TR2P in the SMBRREC function.
9.1.2.4
Lock-out
M14828-18 v5
The SMPPTRC function block is provided with possibilities to initiate lock-out.
The lock-out can be set to only activate the block closing output CLLKOUT or
initiate the block closing output and also maintain the trip signal output TR3P
(latched trip).
Section 9
1MRK 511 423-UEN A
Logic
174
Bay control REC650 2.2 IEC
Application manual