Figure 74:
Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic is the same as for the logic for the double-breaker
configuration.
Signal
S1DC_OP
All disconnectors on bus-section 1 are open.
S2DC_OP
All disconnectors on bus-section 2 are open.
VPS1_DC
The switch status of disconnectors on bus-section 1 is valid.
VPS2_DC
The switch status of disconnectors on bus-section 2 is valid.
EXDU_BB
No transmission error from breaker and a half (BH) that contains the above
information.
8.3.7
Interlocking for busbar earthing switch BB_ES
IP14164-1 v4
8.3.7.1
Application
M15015-3 v7
The interlocking for busbar earthing switch (BB_ES) function is used for one
busbar earthing switch on any busbar parts according to figure
QC
en04000504.vsd
IEC04000504 V1 EN-US
Figure 75:
Switchyard layout BB_ES
M15053-4 v4
The signals from other bays connected to the module BB_ES are described below.
8.3.7.2
Signals in single breaker arrangement
M15053-6 v5
The busbar earthing switch is only allowed to operate if all disconnectors of the
bus-section are open.
Section 8
1MRK 511 423-UEN A
Control
152
Bay control REC650 2.2 IEC
Application manual