Setting
Short Description
Selected
value
Comments
PHiHiLim
High High limit (physical value),
% of SBase
60
High alarm limit that is, extreme
overload alarm, hence it will be
415 MW.
PHiLim
High limit (physical value), in %
of SBase
50
High warning limit that is,
overload warning, hence it will be
371 MW.
PLowLim
Low limit (physical value), in % of
SBase
-50
Low warning limit -500 MW
PLowLowlLim
Low Low limit (physical value), in
% of SBase
-60
Low alarm limit -600 MW
PLimHyst
Hysteresis value in % of range
(common for all limits)
1
Set ±Δ Hysteresis 20 MW that is,
1% of range (2000 MW)
Table 22:
Settings for calibration parameters
Setting
Short Description
Selected
value
Comments
IAmpComp5
Amplitude factor to calibrate
current at 5% of Ir
0.00
IAmpComp30
Amplitude factor to calibrate
current at 30% of Ir
0.00
IAmpComp100
Amplitude factor to calibrate
current at 100% of Ir
0.00
UAmpComp5
Amplitude factor to calibrate
voltage at 5% of Ur
0.00
UAmpComp30
Amplitude factor to calibrate
voltage at 30% of Ur
0.00
UAmpComp100
Amplitude factor to calibrate
voltage at 100% of Ur
0.00
IAngComp5
Angle calibration for current at
5% of Ir
0.00
IAngComp30
Angle pre-calibration for current
at 30% of Ir
0.00
IAngComp100
Angle pre-calibration for current
at 100% of Ir
0.00
Measurement function application for a power transformer
SEMOD54481-61 v9
Single line diagram for this application is given in figure
.
1MRK 511 423-UEN A
Section 10
Monitoring
Bay control REC650 2.2 IEC
201
Application manual