Manual Corrigo Ventilation, revision R
Chapter 15
Settings
73
Shutdown mode
Shutdown mode
P-band: 100.0 °C
I-time: 100 sec
Frost protection temperature
Frost protection
temperature
Frost protection
Active
Setp shutdown: 25°C
P-band active: 5°C
Fast stop at
frost-protection alarm
Yes
"Setp shutdown" is the shutdown mode setpoint.
P-band active 5°C means that the frost protection controller will start overriding the heating output
when the frost protection temperature is less than five degrees above the set frost alarm limit. The
default alarm limit is 7°C. It can be changed in the menu Settings/Alarm settings/Alarm
limits/Alarm limit frost protection.
Exchanger de-icing
De-iceing
P-band: 100 °C
I-time: 100 sec
15.2 Control pressure
Pressure control SAF
Pressure control SAF
P-band: 500 Pa
I-time: 60 sec
Min Output: 0 %
Pressure control EAF
Pressure control EAF
P-band: 500 Pa
I-time: 60 sec
Min Output: 0 %
15.3 Control flow
Flow control SAF
Flow control SAF
P-band: 1000 m3/h
I-time: 60 sec
Min Output: 0 %