60
Chapter 10
Temperature
Manual Corrigo Ventilation, revision R
Support control cooling
Support cooling
Room temp for
Start: 30.0°C
Stop: 28.0°C
Frost protection temperature
Frost protection
Actual: 30.9°C
De-icing exchanger
De-icing exchanger
Actual: 11.2°C
Setpoint: -3.0°C
Hysteresis: 1.0°C
Heat exchanger efficiency monitoring
Efficiency exch.
Actual: 93%
Output exchanger
Actual: 100%
Recirculation (see 5.1.11)
Temp.setpoint when
recirc. (Supply/
Extract/Room)
18.0°C
Offset SAF when
frequency control
and recirculation:
0.0 Pa
"Offset SAF" makes it possible to add an offset to the setpoint during normal operation. If pressure
control has been configured, the offset is set in Pa. If flow control has been configured, it is set in
m
3
/h. If manual control has been configured, the offset is set in percent.
Extra control circuit
(see 5.2)
Extra control circuit
Actual: 21.2°C
Setpoint: 20.0°C
Enthalpy control
Enthalpy indoor:
33.8 KJ/Kg
Enthalpy outdoor:
35.0 KJ/Kg