Manual Corrigo Ventilation, revision R
Chapter 3
Installation and wiring
17
24 V DC supply and 24 V AC relays
3.2.3 Input and output lists
The lists below are intended to be used during commissioning to help you keep track of the desired
input and output functions.
The left column contains a description of the in-/output signal, the middle column displays the name
of the corresponding signal in E tool
©
and the right column shows the text displayed in the Corrigo
controller.
Analogue input signal
Description
E tool
©
Display
Inactive input
Not active
Not active
Outdoor temperature sensor, PT1000 or
0…10V
Outdoor Temp
Outdoortemp
Supply air temperature sensor
Supply Air Temp
Supplytemp
Extract air temperature sensor
Extract Air Temp
Extracttemp
Exhaust air temperature sensor
Exhaust Air Temp
Exhausttemp
Room temperature sensor 1, PT1000 or
0…10V
Room Temp 1
Roomtemp1
Room temperature sensor 2
Room Temp 2
Roomtemp2
CO
2
sensor, 0…10 V DC
CO2 Sensor
CO2
Pressure transmitter supply air, 0…10
V DC
SAF Pressure
SAF pressure
Pressure transmitter extract air, 0…10
V DC
EAF Pressure
EAF pressure
De-icing sensor, heat exchanger
Deicing Temp
Deicingtemp
Frost protection sensor
Frost Protection Temp
Frost prot. temp
Room humidity sensor
Humidity Room
Humidity room
Duct humidity sensor
Humidity Duct
Humidity duct
Outdoor humidity sensor
Humidity Outdoor
Humidity out
Temperature sensor, Extra controller
Extra unit temp
Extra unit temp
External control supply air fan
External control SAF
SAF ext. Ctrl
External control extract air fan
External control EAF
EAF ext. Ctrl
Pressure transmitter supply air 2
SAF Pressure 2
SAF pressure 2