62
Chapter 11
Air control
Manual Corrigo Ventilation, revision R
Chapter 11 Air control
Pressure control SAF and EAF
When using pressure or flow controlled fans, the setpoint can be temperature compensated.
The compensation has the default value 0 Pa, i.e. no compensation is added. The compensation is
linear between the setting points. The compensation can be positive or negative.
The same compensation normally applies to both fans. Using E tool
©
, you can choose to
compensate only the supply air fan.
The same compensation is applied to both "Normal" and "Reduced", which means that you need to
take caution when using this function so the pressure does not become too low or even negative
when running reduced speed.
Depending on the choice of fan control, different combinations of the menus below will be shown.
Pressure control SAF (there are corresponding menus for EAF)
Pressure contr. SAF
Actual: 480 Pa
Setp.: 490 Pa
Submenu "Setpoint"
Pressure contr. SAF
Setp 1/1: 490 Pa
Setp 1/2: 300 Pa
Submenu "Outdoor compensation"
Outd. comp. setp.
-20 °C = -50 Pa
10 °C = 0 Pa
Act. Comp: -5 Pa
Submenu "Extra compensation curve"
Comp.sens.:Roomtemp1
15 °C = 0 Pa
20 °C = 0 Pa
25 °C = 0 Pa
Submenu “Controller output compensation if cooling”
Controller output
comp if cooling
0 at HCOUT= 0%
100 at HCOUT= 0%
Submenu “Controller output compensation if heating”
Controller output
comp if heating
0 at HCOUT= 0%
100 at HCOUT= 0%
The compensation follows the current control quantity, in this case pressure.
Submenu “Controller output compensation”
Controller output
compensation
Not active