
Manual Corrigo Ventilation, revision R
Chapter 17
Configuration
101
17.30.7 Outdoor temp. for control mode change
If the unit is configured for combined Supply air/Room control this menu permits the setting of the
change-over outdoor temperature.
Outdoor temp for
control mode change
13.0°C
17.30.8 Split of optional temp. sequence
Any one of the analogue temperature control output sequences "Y1", "Y2" and "Y3", ”Y1
Heating/Y3 Cooling”, ”Y4-extra sequence” or ”Y5-extra sequence” can be split, for example to
control two heating valves in sequence. The split is always even, 50/50, which means that each part
of the split will have half the part of the P-band assigned to the output. An analogue output must be
assigned to the output signal “Split”. On increasing output demand, the regular output is always run
first and then the output that has been configured as Split.
Split optional
temperature sequence
Y1 Y2 Y3
No split
17.30.9 Fast stop on overheating
If this function is active, the fans will be immediately stopped when there is an overheating alarm,
regardless of the set cool-down time.
Fast stop on alarm
“Electric heating is
overheated”: No
17.30.10 Automatic restart at power-up
The function ”Automatic restart at power-up” makes it possible to block automatic restart of the unit
at power-up. At power-up, the B-alarm ”Restart blocked after power on” is generated. Once this
alarm has been acknowledged, the unit will start.
54%
50%
32%
30%
0%
0%
Controller
signal
Cooling
Heating
Heat
exch.
Output signal
100%
100%
Heat demand