ControlLogix® Controller and Memory Board
37
Publication
1756-IN101J-EN-P - November 2004
Clear a Major Fault
1.
Go online with RSLogix 5000 software and get the fault code.
2.
Determine what to do next:
Fault Type
Fault Code
Action
1
60
A. Clear the fault.
B. Download the project to the controller.
C. Return the controller to the run/remote run mode.
If the problem persists:
A. Before you cycle power to the controller, record the state
of the OK and RS232 LEDs.
B. Contact Rockwell Automation support. See the back of this
publication.
1
61
A. To get diagnostic information about the fault, see
Knowledgebase document A92558072. To get the
document, see the back of this publication.
B. Clear the fault.
C. Download the project to the controller.
D. Return the controller to the run/remote run mode.
none of the
above
none of the
above
A. Clear the fault.
B. Correct the reason for the fault.
C. Return the controller to the run/remote run mode.
1. PROG
2. RUN
3. PROG
To use the keyswitch of the controller to clear a major fault, turn the keyswitch in the
following sequence: