ControlLogix™ AC (74-265V) Output Module
11
Publication
1756-IN028D-EN-P - February 2003
Check the Indicators
1
The indicators show individual I/O status (yellow) for each point and
a bi-colored LED for module "OK" (red/green).
During power up, an indicator test is done and the following occurs:
·
"OK" indicator turns red for 1 second and then turns to
flashing green if it has passed the self-test.
·
I/O status indicators turn ON for a maximum of 2 seconds and
then turn OFF.
This completes installation of the module. Use the following
information to remove the module, if necessary.
Indicator:
Displaying: Means:
Take this action:
OK
Steady green
light
The outputs are actively being
controlled by a system
processor.
None
OK
Flashing
green light
The module has passed
internal diagnostics but is not
actively controlled.
Configure the module.
OK
Flashing red
light
Previously established
communication has timed out.
Check controller and chassis
communication.
OK
Steady red
light
An unrecoverable error has
occurred on the module.
Replace the module.
I/O State
Yellow
The output is active.
None
I/O Fault
Red
A fault has occurred for this
point.
Check this point at the
controller.
AC OUTPUT
ST 0 1 2 3 4 5 6 7
ST 8 9 10 11 12 13 14 15
O
K
FUSE
FUSE
40458-M
Summary of Contents for 1756-ENBT ControlLogix
Page 38: ...18 ControlLogix DC 10 31 2V Input Module Publication 1756 IN031D EN P February 2003 Notes ...
Page 39: ...ControlLogix DC 10 31 2V Input Module 19 Publication 1756 IN031D EN P February 2003 Notes ...
Page 63: ...ControlLogix Voltage Current Input Module 23 Publication 1756 IN039D EN P February 2003 Notes ...
Page 151: ...ControlLogix Voltage Current Output Module 19 Publication 1756 5 42 September 1999 ...