ControlLogix™ AC (74-265V) Output Module
15
Publication
1756-IN028D-EN-P - February 2003
Certifications
(when product is marked)
UL
UL Listed Industrial Control Equipment
CSA
CSA Certified Process Control Equipment
CSA
CSA Certified Process Control Equipment for Class I,
Division 2 Group A,B,C,D Hazardous Locations
FM
FM Approved Equipment for use in Class I Division 2
Group A,B,C,D Hazardous Locations
CE
(5)
European Union 89/336/EEC EMC Directive, compliant
with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
European Union 73/23/EEC LVD Directive, compliant
with:
EN 61131-2; Programmable Controllers
C-Tick
(5)
Australian Radiocommunications Act, compliant
with:
AS/NZS 2064; Industrial Emissions
(1)
The commutating dv/dt of the output voltage (OUTPUT to L2) should not exceed 0.2V/
m
s for loads
under 50mA. The commutating dv/dt rating of the module for loads 50-500mA (OUTPUT TO L2) is
4V/
m
s maximum. If the commutating dv/dt rating of the TRIAC is exceeded, the TRIAC could latch on.
If the commutating dv/dt rating is exceeded in the 10-50mA range, a resistor may be added across the
output and L2. The purpose of this resistor is to increase the total output current to 50mA (I=V/R). At
50mA and above, the module has a higher commutating dv/dt rating. When adding a resistor for mthe
output to L2, be sure it is rated for the power that it will dissipate (P=(V**2)/R). If the commutating
dv/dt rating is exceeded in the 50-500mA range, the L1 AC waveform could be at fault. Be sure the
waveform is a good sinusoid, void if any anomalies such as distorted or flattened sections.
(2)
Maximum wire size requires extended housing - 1756-TBE.
(3)
Use this conductor category information for planning conductor routing as described in the system
level installation manual.
(4)
Refer to publication 1770-4.1
Industrial Automation Wiring and Grounding Guidelines
.
(5)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and
other certification details.
Summary of Contents for 1756-ENBT ControlLogix
Page 38: ...18 ControlLogix DC 10 31 2V Input Module Publication 1756 IN031D EN P February 2003 Notes ...
Page 39: ...ControlLogix DC 10 31 2V Input Module 19 Publication 1756 IN031D EN P February 2003 Notes ...
Page 63: ...ControlLogix Voltage Current Input Module 23 Publication 1756 IN039D EN P February 2003 Notes ...
Page 151: ...ControlLogix Voltage Current Output Module 19 Publication 1756 5 42 September 1999 ...