![AB Quality 1756-ENBT ControlLogix Installation Instructions Manual Download Page 121](http://html.mh-extra.com/html/ab-quality/1756-enbt-controllogix/1756-enbt-controllogix_installation-instructions-manual_450632121.webp)
ControlLogix™ AC (74-265V) Output Module
5
Publication
1756-IN028D-EN-P - February 2003
Use an extended-depth cover (1756-TBE) for applications with heavy
gauge wiring or requiring additional routing space. When using an
IFM, consult the documentation that came with it to connect wiring.
Note the Power Requirements
This module receives power from the 1756 chasis power supply and
requires 2 sources of power from the backplane:
·
400mA at 5.1V dc
·
2mA at 24V dc
Add this current/power value (2.1W) to the requirements of all other
modules in the chassis to prevent overloading the power supply.
IMPORTANT
Before you install your module, you should:
·
install and ground a 1756 chassis and power supply.
·
order and receive an RTB or IFM, and its
components, for your application.
Summary of Contents for 1756-ENBT ControlLogix
Page 38: ...18 ControlLogix DC 10 31 2V Input Module Publication 1756 IN031D EN P February 2003 Notes ...
Page 39: ...ControlLogix DC 10 31 2V Input Module 19 Publication 1756 IN031D EN P February 2003 Notes ...
Page 63: ...ControlLogix Voltage Current Input Module 23 Publication 1756 IN039D EN P February 2003 Notes ...
Page 151: ...ControlLogix Voltage Current Output Module 19 Publication 1756 5 42 September 1999 ...