87
COMMAND
NAME
DESCRIPTION
No.
COMMAND SYNT
AX
Command
Argument 1
Argument 2
Argument 3
Argument 4
Response
Diagnostic
Events
Registers
Read/Set/Reset current value of the Diagnostic
Events Registers
Status Register: (Read/Reset)
Mask Register: (R/W)
Latch Register: (R/W)
See list of the Diagnostic Events below:
0 CPU_TEMP_HIGH 0x0001
1 DP EE INIT ERROR
0x0002
2 AP EE INIT ERROR 0x0004
3 VREF_OUT_OF_RANGE
0x0008
4 FLOW ABOVE LIMIT 0x0010
5 AP OUT OF RANGE
0x0020
6 G TEMP OUT OF RANGE
0x0040
7 ANALOG OUT ALARM 0x0080
8
SER
COMM
FAILURE
0x0100
9 MB COMM F
AILURE
0x0200
A EEPROM F
AILURE
0x0400
B AUTOZERO F
AILURE
0x0800
C AP T
ARE F
AILURE 0x1000
D DP PRESSURE INV
ALID
0x2000
E AP PRESSURE INV
ALID 0x4000
F F
A
TAL_ERROR 0x8000
6
D
E
NO ARGUMENT
(read Diagnostic
Events status
register)
DE:<V
alue>
Example: DE:0x0
R
(reset Diagnostic
Events status
register
to 0x0000)
DER:0x0
M
(Read/Set
Diagnostic
Events Mask
register)
NO ARGUMENT
(read current
settings)
DEM:0x1
<V
alue>
0x0000-0x0FFF
Set new value
NOTE: all 6
characters are
required
DEM:0x101
L
(Read/Set
Diagnostic
Events Latch
register)
NO ARGUMENT
(read current
settings)
DEL:0x1
<V
alue>
0x0000-0x0FFF
Set new value
NOTE: all 6
characters are
required
DEL:0x101
Summary of Contents for DPC
Page 6: ...2...
Page 120: ...116 APPENDIX I COMPONENT DIAGRAM Top Component Side...
Page 121: ...117 Bottom Component Side...