59 / 130
User’s Manual 3PH 10KTL-15KTL-V2
Rev. 1.1 15/03/2021
Identification: MD-AL-GI-00
Rev. 1.1 of 15/03/2021 - Application: GID
Standard Self-test
1)
During normal operation of the inverter, press the “Back” key to enter the main menu.
2)
Press the “OK” key to enter the “Settings” menu.
3)
Press the “Down” key several times until “26. Standard Self-Test” is displayed on the screen.
4)
Press “OK” to start the self-test.
5)
The self-test will now start automatically; once completed, press “Down” to display the self-test
results, as shown in the figure below.