6-2
installation of the grounding copper bar, the feeder grounding clip and the lightning
arrester.
B
T
S
Grounding
cable 50mm
2
Outdoor
grounding bar
Grounding
cable 35mm
Feeder
grounding clip
Iron tower
platform
U
Feeder
Grounding cable
of the Lighting
arrester frame
Lightning
arrester frame
D
C
p
ow
er
fra
m
e
O
the
r e
qui
pme
nt
2
Indoor
grounding bar
Protection ground of any equipment
(including cabling racks) inside the
equipment room shall be connected
to the indoor grounding bar.
Fig. 6.1-1 Wiring for the BTS Ground
6.2 Installing the BTS Grounding System
6.2.1 Installing the Outdoor Grounding Copper Bar
The outdoor grounding copper bar is used for lightning protection grounding. It is
usually installed on the wall outside the feeder window. The best place for it is right