26
DEFR
OS
TING
F31
Start defrosting temperature
(in °C)
-10 - 0
-7
F32
Stop defrosting temperature
(en °C)
5 - 35
15
F33
Start defrosting duration (min)
1 -120
25
F34
Maximum defrosting duration (min)
3 - 20
10
F35
Default temperature start defrosting (in
°C)
-10 - 20
7
F36
Alarm delay time after defrosting
0 - 120
3
F37
4-way valve mode
0: OFF
1: ON
0
CONTR
OL
F38
Remote Cooling mode
0: setpoint not considered
1: setpoint considered
1
F39
Remote Heating mode
0: setpoint not considered
1: setpoint considered
1
ELE
CTRICAL C
ONNE
CTIONS
F40
Thermal protection (A)
0 - 40
0: not active
Depending on
model
TD35: 20
TD45: 26
TD60: 34
TD90: 26
TD120: 34
F42
Current(s) delay time
0 - 30
3
F44
% of phase(s) current imbalance
5 - 50
20
F45
Delay time of the absence of phase(s)
alarm
0 - 60
3
F46
Delay time of the phase(s) imbalance
alarm
0 - 30
2
F47
Delay time of the phase(s) fault alarm
0 - 30
2
F49
Autostart function (appliance
automatically resets following a power
cut)
0: deactivated
1: activated
1
F50
Heating Priority
0: pump deactivated
1: pump activated
(voltage 220 V)
1
FIL
TER PUMP
F51
Filtration pump start-up delay before
compressor start-up (min)
1 - 10
3
F52
Filtration pump stop-delay after
compressor stop (min)
0 - 10
3
F53
Water temperature check interval (min)
0 - 99
60
F54
Filtration pump operating time (min)
0 -99
5
F55
Compressor discharge temperature
protection
90 - 135
115
F56
Water flow detector
0: deactivated
1: activated
1
F57
Fan thermal relay
0: deactivated
1: activated
1
Содержание WH000456
Страница 2: ......