27
ALARMS AND CALIBRA
TION
F59
Minimum ambient temperature for
switching on the electrical resistance (in
°C)
-10 - 20
5
F60
Maximum temperature difference
between water inlet and outlet
temperature (in °C)
0 - 20
4
F63
Calibration of the defrosting temperature
sensor 1 (in °C)
-20 - 20
0
F64
Calibration of the defrosting temperature
sensor 2 (in °C)
-20 - 20
0
F65
Calibration of the ambient temperature
sensor (in °C)
-20 - 20
0
F66
Calibration of the compressor 1 discharge
temperature sensor (in °C)
-20 - 20
0
F67
Calibration of the compressor 2 discharge
temperature sensor (in °C)
-20 - 20
0
F68
Calibration of the compressor 1 suction
sensor (in °C)
-20 - 20
0
F69
Calibration of the compressor 2 suction
sensor (in °C)
-20 - 20
0
ELE
CTR
ONIC EXP
ANSION V
AL
VE
F70
Electronic expansion valve
0: deactivated
1: activated
0
F71
Refrigerant gas
0: R-410-A
1: R-407-C
0
F72
Maximum output voltage (V)
0.5 - 5.0
4.5
F73
Maximum sensor pressure (MPa)
0 - 5
4.6
F74
Initial position of the valve in Cooling
mode (step)
100 - 480
240
F75
Initial position of the valve in Heating
mode (step)
100 - 480
240
F76
Overheating adjustment time
0 - 120
30
F77
Step setting (fine)
0 - 10
1
F78
Step setting (average)
0 - 10
3
F79
Step setting (rough)
0 - 10
6
F80
Overheating in Heating mode (°C)
3 - 20
6
F81
Overheating in Cooling mode (°C)
3 - 25
10
F82
Maximum authorised evaporation
temperature (°C)
10 -100
20
F83
High evaporation temperature (°C)
1 - 5
2
F84
High evaporation temperature delay (min)
1 - 3
2
SY
STEM
SET
TINGS
F86
Test time
0 - 999
OFF: no test time
OFF
F87
Reset total operating time
YES
NO
NO
F88
Reset factory settings
YES
NO
NO
APPLIANCE
INF
ORMA
TION
F90
Show the board model
F91
Show the board's software version
F92
Show the screen model
F93
Show the screen software version
F96
Set the time
F00
Exit
EN