background image

Page 22

ENGLISH

  

 

 Zodiac

®

 Jandy

® 

Heat Pumps Model EE-Ti   

|

   Installation and Operation Manual

to select. Use the

 

up

 or 

down

 

button to scroll 

to display 

seleCt displaY liGHt liGHt 

oFF

, this option allows the display light to turn 

off, press the

 

Menu 

button to select. Use the

 

up

 or 

down

 

button to scroll to display 

seleCt 

displaY liGHt liGHt on

,

 

this option allows 

the display light to turn on, press the

 

Menu 

button to select. Press 

pool

 or 

spa

 to exit the 

User Setup mode.

5.5 

set point lockout

Make sure the control is in the 

on

 mode (

pool

 

or 

spa

), press and hold the 

up

 and 

down

 buttons for 

5 seconds. The set point will be locked and the control 

will operate in the mode it was in when the Set Point 

Lockout occurred. If an attempt to change the set point 

is made while the control is in Set Point Lockout, the 

control will display 

set point loCKed

. To unlock 

the Set Point Lockout, press and hold the 

up

 and 

down 

buttons for 5 seconds. The unit will display 

set point   

unloCKed

.

5.6 

Water pressure switch adjustment

  Caution

The water pressure switch should be adjusted 

to turn the heater off when the pump is off. 

Setting the switch to close at too low of a flow 

can damage the appliance. Adjust the switch 

to turn the heater off, not on.

  attention

Le manocontact de pression d’eau doit être 

réglé de façon à ce que l’appareil cesse 

de fonctionner si la pompe s’arrête. Si le 

manocontact est réglé pour se fermer lorsque 

le débit d’eau est trop faible, l’appareil risque 

de s’endommager. Réglez le manocontact 

pour qu’il arrête l’appareil, et non pour qu’il le 

mette en marche.

  preCauCiÓn

El interruptor de la presión del agua, deberá 

ajustarse de forma que el calentador se apague 

cuando se apague la bomba. La calibración del 

interruptor para que pueda apagarse con flujos 

demasiado bajos podría estropear el equipo. 

Ajuste el interruptor para apagar el calentador, 

no para encenderlo.

The pressure switch is preset at the factory for 

activation at 2 psi (14 kPa). This is the minimum 

setting for the water pressure switch and works for 

all basic installations as shown previously in Section 

3.1 and Section 3.5 in this manual. Only adjust the 

water pressure switch if the heat pump does not 

operate 

when the proper flow is applied to unit 

or if 

the heat pump does not shut off when the filter pump 

is off. Occasionally, unusual plumbing configurations 

or necessary restrictions in the plumbing may cause 

pressure sensing problems. In these rare situations, the 

plumbing system configuration may require adjustment 

of the water pressure switch.

Adjustment of the pressure switch may be 

necessary if any part of the filter system piping is 3 feet 

(1 m) or more above the top of the heat pump jacket.

Do not adjust the pressure switch if the heat pump 

is installed more than 5 feet (1.5 m) above or 10 feet  

(3 m) below the pool surface. Consult your local Zodiac 

dealer for recommendations.

note

  If the heat pump is installed more than 5 feet 

(1.5 m) above or 10 feet (3 m) below the pool 

surface a flow switch must be used. Please 

order Zodiac p/n R0509700.

On some installations, the piping from the heat 

pump to the pool is very short. The back pressure 

could be too low to trigger the pressure switch. If this 

happens, it may be necessary to install a directional 

fitting or elbows where the return line enters the 

pool. This will increase back pressure enough for the 

heat pump to operate properly. If this configuration 

is necessary, be sure to check that the system flow is 

above the minimum requirement of 30 gpm (114 lpm) 

after the direction fitting or elbow has been installed. 

Make sure the pool filter is clean before making 

any pressure switch adjustment: A dirty filter will 

restrict the water flow and the pressure switch cannot be 

adjusted properly. 

To adjust the pressure switch: 

1.   Be sure that all valves in the system are set to 

allow water flow through the heat pump. Start the 

filter pump.

2.  Set the heat pump control to call for heat. Set the 

heat pump control to the POOL HEAT mode. 

3.  If the heat pump control displays “NO FLOW”, 

then the flow in the system may be below the 

minimum flow of 30 gpm (114 lpm) needed for 

the safe operation of the heat pump. Investigate 

and correct any flow problems before adjusting the 

water pressure switch.

4.  Remove the heat pump’s control access panel. The 

water pressure switch is located in the lower left 

corner of the control compartment.

5.  After confirming the flow rate is at a minimum 

of 30 gpm (114 lpm), slowly rotate the thumb 

wheel on the water pressure switch in a 

counterclockwise 

direction until the “NO FLOW” 

indicator disappears from the control display. 

Remember that there is a time delay before the 

Содержание Jandy EE-Ti

Страница 1: ...n of R410A refrigerant In the event no such state or local requirement exists the installer or maintainer must be a professional with sufficient experience in pool equipment installation and maintenan...

Страница 2: ......

Страница 3: ...17 4 5 1 1 Install the Remote Pool Off Spa Selector 17 4 5 1 2 Configure the Control Panel 17 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 17 4 5 2 1 Configure the AquaLink RS Control System 1...

Страница 4: ...4 Figure 10 Example of MAINTAIN TEMP Wiring to the Time Clock 15 Figure 11 EE Ti Heat Pump Front View 15 Figure 12a Remote Pool Off Spa Connection 3 Wire Connection 16 Figure 12b AquaLink RS or Remote...

Страница 5: ...in drowning Section 1 General Information 1 1 Introduction This manual provides installation and operation instructions for the Zodiac EE Ti models of heat pumps Read these installation and operation...

Страница 6: ...without sacrificing comfort 1 The American Red Cross recommends a maximum water temperature of 78 F 25 C Use an accurate pool thermometer A difference of 4 F 2 C between 78 F and 82 F 26 C and 28 C w...

Страница 7: ...adhered to Water Pipe Heater Connection Plastic 2 PVC Unions included Flow Rate Maximum Optimum Minimum 125 gpm 475 lpm 60 gpm 230 lpm 30 gpm 114 lpm Note If a flow switch is installed R0509700 do no...

Страница 8: ...PRESSURE ALARM 650 PSI reset to 460 PSI REFRIGERANT LOW PRESSURE ALARM HEATING UNITS 58 PSI reset to 127 PSI REFRIGERANT LOW PRESSURE ALARM REVERSE UNITS 35 PSI reset to 74 PSI LOW WATER FLOW ALARM 3...

Страница 9: ...o public access areas 2 2 2 Clearances The heat pump must be placed to provide clearances on all sides for maintenance and inspection See Table 2 Side of Heat pump Minimum Clearances for Operation Rec...

Страница 10: ...ts of water may run off from a roof into the unit Sharp sloping roofs without gutters will allow massive amounts of rain water mixed with debris from the roof to be forced through the unit A gutter or...

Страница 11: ...rrence 3 2 Water Connections at Heat Pump Shipping plugs have been installed in the water inlet and outlet ports of the heat pump at the factory Before installing any plumbing remove the shipping plug...

Страница 12: ...All plumbing on multiple heat pump installations must be done in parallel see Figures 6 and 7 An equal flow of water to each heat pump is important for optimum operation Note It may be necessary to ad...

Страница 13: ...L OR SPA CHEMICAL FEEDER TO POOL OR SPA CHECK VALVE OR OPTIONAL CHLORINE GENERATION SYSTEM JANDY AQUAPURE SHOWN MANUAL BYPASS VALVE CHEMICAL LOOP VENT FOR INDOOR INSTALLATION ONLY HEATER HEAT PUMP FRO...

Страница 14: ...on and Operation Manual Figure 6 Two 2 Heat Pump Plumbing Layout Figure 7 Four 4 Heat Pump Plumbing Layout Manual Bypass Valve 2 PVC 3 PVC Optional Isolation Valves From Filter To Pool Manual Bypass V...

Страница 15: ...ITE BLANC BLANCO Y YELLOW JAUNE AMARILLO BR BK BL Y W BR 24 BK O O Y 24 W FACTORY INSTALLED 230 VAC FIELD INSTALLED 230 VAC FACTORY 24 VAC HARNESS FACTORY 24 VAC FACTORY OPTIONAL 24 VAC FACTORY OPTION...

Страница 16: ...TIONAL 230 VAC BK BLACK NOIR NEGRO BL BLUE BLEU AZUL BR BROWN MARRON MARRON BR W BROWN WITH WHITE TRACE MARRON AVEC UNE TRACE DE BLANC MARRON Y BLANCO GR GREEN VERT VERDE O ORANGE ORANGE ANARANJADO R...

Страница 17: ...Example of MAINTAIN TEMP Wiring to the Time Clock INTERMATIC MODEL T104 MECHANICAL TIMER NOT PROVIDED WITH HEAT PUMP INTERMATIC MODEL T104 NOT PROVIDED WITH HEAT PUMP WIRE CONNECTIONS SHOWN AS AN EXA...

Страница 18: ...o Figures 8 and 9 6 Connect the ground wire to the ground lug provided in the electrical compartment 7 Replace the cover of the junction box 8 Replace the service access panel and replace the screws t...

Страница 19: ...the Remote options When you reach HI LO COM press the MENU button to select the remote Press POOL or SPA to exit the Service Setup mode 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 4 5 2 1 Co...

Страница 20: ...ed up on the red terminal bar with the four 4 wires coming from the indoor controller NOTE If you need to install more than two 2 wires in each terminal order a Zodiac Multiplex PCB Kit 1 2 3 4 RED BL...

Страница 21: ...e inspeccione el equipo y reemplace cualquier parte del sistema de control que haya estado debajo del agua CAUTION Keep all objects off the top of the heat pump Blocking air flow could damage the unit...

Страница 22: ...er a 5 minute delay the control will start the heat pump and the associated right LED will light RED 5 2 5 Spa Mode Optional Maintain Heat If connected the Maintain Heat mode allows the heat pump to m...

Страница 23: ...r Down button to display SELECT USER SETUP LANGUAGE Press the MENU button The SELECT LANGUAGE ENGLISH default language appears use the Up or Down button to scroll through the language options When you...

Страница 24: ...o unit or if the heat pump does not shut off when the filter pump is off Occasionally unusual plumbing configurations or necessary restrictions in the plumbing may cause pressure sensing problems In t...

Страница 25: ...ment It is recommended to change the spa water every 60 days for light usage and every 30 days if usage is heavy 6 2 Winterizing CAUTION Failure to winterize could cause damage to the heat pump and wi...

Страница 26: ...conditions The following basic guidelines are suggested for your inspection 1 Keep the top and surrounding areas of the heat pump clear of all debris 2 Keep all plants and shrubs trimmed and away from...

Страница 27: ...gerant used in the AE Ti heat pump Therefore R 410A should NEVER be used in any of the AE Ti heat pumps The EPA requires certification to purchase or use R 410A It is recommended that service personne...

Страница 28: ...ot heat call for service Heat pump does not run and control board displays FAULT NO FLOW Verify circulating pump is on and all necessary valves are in the correct positions Verify filter and skimmers...

Страница 29: ...ressure builds too high the high pressure switch will open causing the heat pump to shut off immediately The control will sense this fault condition and shut off the compressor until the switch re clo...

Страница 30: ...lacement Kit 2X7 2500 R0561407 20 Heat Exchanger Replacement Kit 2X8 3000 R0561408 21 Compressor 40K 1 Phase 1500 R0510300 21 Compressor 61K 1 Phase 2000 R0510400 21 Compressor 68K 1 Phase 2500 R05105...

Страница 31: ...ploded View 26 12 11 These pressure switches are installed in the refrigerant line near the compressor R E D W I R E B L U E W I R E Y E L L O W W I R E O R A N G E W I R E 2 32 6 7 9 31 8 5 B 21 18 A...

Страница 32: ...tems Inc 2620 Commerce Way Vista CA 92081 1 800 822 7933 www ZodiacPoolSystems com ZODIAC is a registered trademark of Zodiac International S A S U used under license All trademarks referenced herein...