Page 19

ENGLISH

  

 

 Zodiac

®

 Jandy

® 

Heat Pumps Model EE-Ti   

|

   Installation and Operation Manual

ee-ti Heat pump power 

interface software rev.

aqualink

®

 rs software 

revision

3.0 or later

n or later

note 

If connecting more than two (2) items to the RS 

Power Center red, 4-pin connector, a Multiplex 

PCB is required.

4.5.4   Connection to a secondary user 

interface

1.   Turn off the power to the heat pump.
2.   Remove the four (4) screws that attach the service 

access panel to the heat pump and remove the 

cover to the junction box.  See Figure 11.

3.   Run four (4) 22 AWG solid copper wires into the 

conduit labeled “Low Voltage Connection” located 

on the lower right hand side of the heat pump.  See 

Figure 11.  The wires may be up to 300 feet (91.4 

m) in length.

4.   Connect the wires to the 4 position terminal on 

the upper left hand corner of the Power Interface 

PC Board, labeled “User Interface1”.  The wires 

will be added to the existing wiring to the User 

Interface installed on the heat pump.

5.    Ensure the wiring is consistent when connecting 

the wires to the second User Interface.  For 

example, BK goes to BK, O goes to O, etc.

6.   Re-install the junction box cover and service 

access panel and restore power to the heat pump.

section 5.  operation

 Caution

Do not use this heat pump if any part has 

been under water. Immediately call a qualified 

service technician to inspect the heater and 

replace any part of the control system which 

has been under water.

  

attention

N’utilisez pas cet appareil s’il a été plongé 

dans l’eau, même partiellement. Faites 

inspecter l’appareil par un technicien qualifié et 

remplacez toute partie du système de contrôle 

et toute commande qui ont été plongés dans 

l’eau.

  preCauCiÓn

No utilice esta bomba de calor si algunos de 

sus componentes han estado debajo del agua. 

Póngase inmediatamente en contacto con un 

técnico de mantenimiento cualificado para que 

inspeccione el equipo y reemplace cualquier 

parte del sistema de control que haya estado 

debajo del agua.

  Caution

Keep all objects off the top of the heat pump. 

Blocking air flow could damage the unit and 

may void the warranty.
 

 

      

attention

Ne posez aucun objet sur le dessus de 

l’appareil. Il pourrait empêcher la circulation de 

l’air, ce qui risquerait d’endommager l’appareil 

et d’annuler la garantie.

  preCauCiÓn

Mantenga todos los objetos fuera de la parte 

superior de la bomba de calor. La obstrucción 

del flujo de aire podría dañar la unidad y 

anular la garantía.

5.1 

initial start-up precautions

Be sure that there is water in the pool and that the 

surface level is above the skimmer or other inlet of the 

pool’s filter system.

With any new pool or spa installation, operate 

the filter pump with the heat pump off long enough 

to completely clean the water. This will remove any 

installation residue from the water.

Clean the filter at the end of this operation before 

starting the heat pump. When raising the temperature 

of a cold pool, program the time clock to run the pump 

continuously.

This lets the filter system and heat pump operate 

continuously until the water reaches the temperature 

setting on the temperature control. When that happens, 

the heat pump will automatically shut off, but the filter 

pump will keep running.

5.2 

operating the Controller

Your new EE-Ti heat pump is controlled by an 

advanced microprocessor based controller that provides 

a sophisticated yet simple interface to operate your heat 

pump for maximum efficiency and enjoyment of your 

pool. To locate the control buttons, see Figure 15.

5.2.1  off Mode

When the control panel is turned off, the screen 

displays 

Heat puMp is oFF

 

press pool or 

spa

.

5.2.2  pool Mode - (normal Heat)

To enable the pool mode, press 

pool

. The 

associated left green LED indicator will light and the 

unit will display 

set:xxx°

.

note

 

XXX 

represents the current temperature setting 

on the control. The default setting for pool 

temperature is 80°F (26°C).

You can change the temperature set point by 

Содержание Jandy EE-Ti

Страница 1: ...n of R410A refrigerant In the event no such state or local requirement exists the installer or maintainer must be a professional with sufficient experience in pool equipment installation and maintenan...

Страница 2: ......

Страница 3: ...17 4 5 1 1 Install the Remote Pool Off Spa Selector 17 4 5 1 2 Configure the Control Panel 17 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 17 4 5 2 1 Configure the AquaLink RS Control System 1...

Страница 4: ...4 Figure 10 Example of MAINTAIN TEMP Wiring to the Time Clock 15 Figure 11 EE Ti Heat Pump Front View 15 Figure 12a Remote Pool Off Spa Connection 3 Wire Connection 16 Figure 12b AquaLink RS or Remote...

Страница 5: ...in drowning Section 1 General Information 1 1 Introduction This manual provides installation and operation instructions for the Zodiac EE Ti models of heat pumps Read these installation and operation...

Страница 6: ...without sacrificing comfort 1 The American Red Cross recommends a maximum water temperature of 78 F 25 C Use an accurate pool thermometer A difference of 4 F 2 C between 78 F and 82 F 26 C and 28 C w...

Страница 7: ...adhered to Water Pipe Heater Connection Plastic 2 PVC Unions included Flow Rate Maximum Optimum Minimum 125 gpm 475 lpm 60 gpm 230 lpm 30 gpm 114 lpm Note If a flow switch is installed R0509700 do no...

Страница 8: ...PRESSURE ALARM 650 PSI reset to 460 PSI REFRIGERANT LOW PRESSURE ALARM HEATING UNITS 58 PSI reset to 127 PSI REFRIGERANT LOW PRESSURE ALARM REVERSE UNITS 35 PSI reset to 74 PSI LOW WATER FLOW ALARM 3...

Страница 9: ...o public access areas 2 2 2 Clearances The heat pump must be placed to provide clearances on all sides for maintenance and inspection See Table 2 Side of Heat pump Minimum Clearances for Operation Rec...

Страница 10: ...ts of water may run off from a roof into the unit Sharp sloping roofs without gutters will allow massive amounts of rain water mixed with debris from the roof to be forced through the unit A gutter or...

Страница 11: ...rrence 3 2 Water Connections at Heat Pump Shipping plugs have been installed in the water inlet and outlet ports of the heat pump at the factory Before installing any plumbing remove the shipping plug...

Страница 12: ...All plumbing on multiple heat pump installations must be done in parallel see Figures 6 and 7 An equal flow of water to each heat pump is important for optimum operation Note It may be necessary to ad...

Страница 13: ...L OR SPA CHEMICAL FEEDER TO POOL OR SPA CHECK VALVE OR OPTIONAL CHLORINE GENERATION SYSTEM JANDY AQUAPURE SHOWN MANUAL BYPASS VALVE CHEMICAL LOOP VENT FOR INDOOR INSTALLATION ONLY HEATER HEAT PUMP FRO...

Страница 14: ...on and Operation Manual Figure 6 Two 2 Heat Pump Plumbing Layout Figure 7 Four 4 Heat Pump Plumbing Layout Manual Bypass Valve 2 PVC 3 PVC Optional Isolation Valves From Filter To Pool Manual Bypass V...

Страница 15: ...ITE BLANC BLANCO Y YELLOW JAUNE AMARILLO BR BK BL Y W BR 24 BK O O Y 24 W FACTORY INSTALLED 230 VAC FIELD INSTALLED 230 VAC FACTORY 24 VAC HARNESS FACTORY 24 VAC FACTORY OPTIONAL 24 VAC FACTORY OPTION...

Страница 16: ...TIONAL 230 VAC BK BLACK NOIR NEGRO BL BLUE BLEU AZUL BR BROWN MARRON MARRON BR W BROWN WITH WHITE TRACE MARRON AVEC UNE TRACE DE BLANC MARRON Y BLANCO GR GREEN VERT VERDE O ORANGE ORANGE ANARANJADO R...

Страница 17: ...Example of MAINTAIN TEMP Wiring to the Time Clock INTERMATIC MODEL T104 MECHANICAL TIMER NOT PROVIDED WITH HEAT PUMP INTERMATIC MODEL T104 NOT PROVIDED WITH HEAT PUMP WIRE CONNECTIONS SHOWN AS AN EXA...

Страница 18: ...o Figures 8 and 9 6 Connect the ground wire to the ground lug provided in the electrical compartment 7 Replace the cover of the junction box 8 Replace the service access panel and replace the screws t...

Страница 19: ...the Remote options When you reach HI LO COM press the MENU button to select the remote Press POOL or SPA to exit the Service Setup mode 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 4 5 2 1 Co...

Страница 20: ...ed up on the red terminal bar with the four 4 wires coming from the indoor controller NOTE If you need to install more than two 2 wires in each terminal order a Zodiac Multiplex PCB Kit 1 2 3 4 RED BL...

Страница 21: ...e inspeccione el equipo y reemplace cualquier parte del sistema de control que haya estado debajo del agua CAUTION Keep all objects off the top of the heat pump Blocking air flow could damage the unit...

Страница 22: ...er a 5 minute delay the control will start the heat pump and the associated right LED will light RED 5 2 5 Spa Mode Optional Maintain Heat If connected the Maintain Heat mode allows the heat pump to m...

Страница 23: ...r Down button to display SELECT USER SETUP LANGUAGE Press the MENU button The SELECT LANGUAGE ENGLISH default language appears use the Up or Down button to scroll through the language options When you...

Страница 24: ...o unit or if the heat pump does not shut off when the filter pump is off Occasionally unusual plumbing configurations or necessary restrictions in the plumbing may cause pressure sensing problems In t...

Страница 25: ...ment It is recommended to change the spa water every 60 days for light usage and every 30 days if usage is heavy 6 2 Winterizing CAUTION Failure to winterize could cause damage to the heat pump and wi...

Страница 26: ...conditions The following basic guidelines are suggested for your inspection 1 Keep the top and surrounding areas of the heat pump clear of all debris 2 Keep all plants and shrubs trimmed and away from...

Страница 27: ...gerant used in the AE Ti heat pump Therefore R 410A should NEVER be used in any of the AE Ti heat pumps The EPA requires certification to purchase or use R 410A It is recommended that service personne...

Страница 28: ...ot heat call for service Heat pump does not run and control board displays FAULT NO FLOW Verify circulating pump is on and all necessary valves are in the correct positions Verify filter and skimmers...

Страница 29: ...ressure builds too high the high pressure switch will open causing the heat pump to shut off immediately The control will sense this fault condition and shut off the compressor until the switch re clo...

Страница 30: ...lacement Kit 2X7 2500 R0561407 20 Heat Exchanger Replacement Kit 2X8 3000 R0561408 21 Compressor 40K 1 Phase 1500 R0510300 21 Compressor 61K 1 Phase 2000 R0510400 21 Compressor 68K 1 Phase 2500 R05105...

Страница 31: ...ploded View 26 12 11 These pressure switches are installed in the refrigerant line near the compressor R E D W I R E B L U E W I R E Y E L L O W W I R E O R A N G E W I R E 2 32 6 7 9 31 8 5 B 21 18 A...

Страница 32: ...tems Inc 2620 Commerce Way Vista CA 92081 1 800 822 7933 www ZodiacPoolSystems com ZODIAC is a registered trademark of Zodiac International S A S U used under license All trademarks referenced herein...

Отзывы: