A Maintain Temp Relay is required (provided) and 

the feature must be enabled.

When the temperature of the water rises above the 

desired temperature setting, the control will then turn on 

the unit and the associated right green LED will light.

To operate in pool mode with the Maintain Chill 

feature, press 

pool

, then press 

Menu

, then press 

the 

down

 button until 

Maintain pool CHill 

is 

displayed, press the 

Menu

 button. The associated 

left green LED indicator will light and the unit will 

display 

set:xxx°

. Change the temperature set point 

by pressing the 

up

 or 

down

 button until the desired set 

point is displayed. After 5 seconds of inactivity, the new 

set point is stored in memory. 

5.3.3  spa Mode - (optional Maintain Chill)

If connected, the Maintain Chill mode allows the 

heat pump to monitor the temperature of the water 24 

hours a day by turning the spa pump on and sampling 

the water temperature.

A Maintain Temp Relay is required (provided) and 

the feature must be enabled.

When the water temperature rises above the 

programmed temperature set point, the control will start 

the heat pump.

To operate in the spa mode with the Maintain Chill 

feature, press 

spa

, then press 

Menu

, press the 

down

 

button until 

Maintain spa CHill 

is displayed, 

press the 

Menu

 button. The associated left green LED 

indicator will light and the unit will display 

set:xxx°

Change the temperature set point by pressing the 

up

 

or 

down

 button until the desired set point is reached.  

After 5 seconds of inactivity, the new set point is stored 

in memory.

5.4 

user setup options

The User Setup options allow the user to select 

specific Languages, Temperature Scale, Spa Timer, and 

Display Light options.

5.4.1  language setup

1.  Make sure the control is in the 

oFF

 mode.

2.  To enter the User Setup mode, press and hold the 

Menu

 button for 5 seconds. 

note

  The display will revert back to 

oFF

 after one 

minute since the last key press.

3.  To select a language, use the 

up

 or 

down

 button 

to display 

seleCt user setup lanGuaGe

Press the 

Menu

 button. The 

seleCt 

lanGuaGe enGlisH 

(default language) 

appears, use the

 

up

 or 

down

 

button to scroll 

through the language options. When you reach the 

desired language, press the

 

Menu 

button to select 

the language. Press 

pool

 or 

spa

 to exit the 

User Setup mode.

5.4.2  temperature scale setup

1.  Make sure the control is in the 

oFF

 mode.

2.  To enter the User Setup mode, press and hold the 

Menu

 button for 5 seconds. 

3.  To select temperature scale, use the

 

up

 or 

down

 

button to scroll through to display 

seleCt 

user setup teMperature sCale

. Press 

the 

Menu 

button. The 

seleCt teMp sCale 

°F 

(default temperature scale) appears, use the

 

up

 or 

down

 

button to scroll through the scale 

options.

 

When you reach the desired temperature 

scale, press the

 

Menu 

button to select. Press 

pool

 or 

spa

 to exit the User Setup mode.

5.4.3  spa timer setup

1.  Make sure the control is in the 

oFF

 mode.

2.  To enter the User Setup mode, press and hold the 

Menu

 button for 5 seconds. 

3.  To select spa timer, use the

 

up

 or 

down

 

button to 

scroll through to display 

seleCt user setup 

spa tiMer

.

 

Press the 

Menu

 button. The 

seleCt spa tiMer Continuous 

(default 

spa timer setting)

 

is displayed. To turn the spa 

on or off indefinitely, press the

 

Menu 

button to 

select. 

 

To select the length of time for the spa to run, 

use the

 

up

 or 

down

 

button to scroll to display 

seleCt spa tiMer tiMe seleCtion

.

 

Press 

the

 

Menu 

button to select.

 

The display 

seleCt 

spa tiMe 01:00 Hrs 

(default time setting) is 

displayed. Use the

 

up

 or 

down

 

button to select 

the length of time for the spa to run (between 

00:15 to 23:00 hours incremented by 00:15 

minutes). Press the

 

Menu 

button to select how 

long the spa will run. Press 

pool

 or 

spa

 to exit 

the User Setup mode.

5.4.4  display light setup

1.  Make sure the control is in the 

oFF

 mode.

2.  To enter the User Setup mode, press and hold the 

Menu

 button for 5 seconds. 

3.  To select display light setup, use the

 

up

 or 

down

 

button to scroll through to display 

seleCt 

user setup displaY liGHt

. Press the 

Menu

 button. The 

seleCt displaY liGHt 

2 Min tiMeout 

(default display light setting)

 

is 

displayed. This option allows the display light to 

turn off after 2 minutes. Press the

 

Menu 

button 

Содержание Jandy EE-Ti

Страница 1: ...n of R410A refrigerant In the event no such state or local requirement exists the installer or maintainer must be a professional with sufficient experience in pool equipment installation and maintenan...

Страница 2: ......

Страница 3: ...17 4 5 1 1 Install the Remote Pool Off Spa Selector 17 4 5 1 2 Configure the Control Panel 17 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 17 4 5 2 1 Configure the AquaLink RS Control System 1...

Страница 4: ...4 Figure 10 Example of MAINTAIN TEMP Wiring to the Time Clock 15 Figure 11 EE Ti Heat Pump Front View 15 Figure 12a Remote Pool Off Spa Connection 3 Wire Connection 16 Figure 12b AquaLink RS or Remote...

Страница 5: ...in drowning Section 1 General Information 1 1 Introduction This manual provides installation and operation instructions for the Zodiac EE Ti models of heat pumps Read these installation and operation...

Страница 6: ...without sacrificing comfort 1 The American Red Cross recommends a maximum water temperature of 78 F 25 C Use an accurate pool thermometer A difference of 4 F 2 C between 78 F and 82 F 26 C and 28 C w...

Страница 7: ...adhered to Water Pipe Heater Connection Plastic 2 PVC Unions included Flow Rate Maximum Optimum Minimum 125 gpm 475 lpm 60 gpm 230 lpm 30 gpm 114 lpm Note If a flow switch is installed R0509700 do no...

Страница 8: ...PRESSURE ALARM 650 PSI reset to 460 PSI REFRIGERANT LOW PRESSURE ALARM HEATING UNITS 58 PSI reset to 127 PSI REFRIGERANT LOW PRESSURE ALARM REVERSE UNITS 35 PSI reset to 74 PSI LOW WATER FLOW ALARM 3...

Страница 9: ...o public access areas 2 2 2 Clearances The heat pump must be placed to provide clearances on all sides for maintenance and inspection See Table 2 Side of Heat pump Minimum Clearances for Operation Rec...

Страница 10: ...ts of water may run off from a roof into the unit Sharp sloping roofs without gutters will allow massive amounts of rain water mixed with debris from the roof to be forced through the unit A gutter or...

Страница 11: ...rrence 3 2 Water Connections at Heat Pump Shipping plugs have been installed in the water inlet and outlet ports of the heat pump at the factory Before installing any plumbing remove the shipping plug...

Страница 12: ...All plumbing on multiple heat pump installations must be done in parallel see Figures 6 and 7 An equal flow of water to each heat pump is important for optimum operation Note It may be necessary to ad...

Страница 13: ...L OR SPA CHEMICAL FEEDER TO POOL OR SPA CHECK VALVE OR OPTIONAL CHLORINE GENERATION SYSTEM JANDY AQUAPURE SHOWN MANUAL BYPASS VALVE CHEMICAL LOOP VENT FOR INDOOR INSTALLATION ONLY HEATER HEAT PUMP FRO...

Страница 14: ...on and Operation Manual Figure 6 Two 2 Heat Pump Plumbing Layout Figure 7 Four 4 Heat Pump Plumbing Layout Manual Bypass Valve 2 PVC 3 PVC Optional Isolation Valves From Filter To Pool Manual Bypass V...

Страница 15: ...ITE BLANC BLANCO Y YELLOW JAUNE AMARILLO BR BK BL Y W BR 24 BK O O Y 24 W FACTORY INSTALLED 230 VAC FIELD INSTALLED 230 VAC FACTORY 24 VAC HARNESS FACTORY 24 VAC FACTORY OPTIONAL 24 VAC FACTORY OPTION...

Страница 16: ...TIONAL 230 VAC BK BLACK NOIR NEGRO BL BLUE BLEU AZUL BR BROWN MARRON MARRON BR W BROWN WITH WHITE TRACE MARRON AVEC UNE TRACE DE BLANC MARRON Y BLANCO GR GREEN VERT VERDE O ORANGE ORANGE ANARANJADO R...

Страница 17: ...Example of MAINTAIN TEMP Wiring to the Time Clock INTERMATIC MODEL T104 MECHANICAL TIMER NOT PROVIDED WITH HEAT PUMP INTERMATIC MODEL T104 NOT PROVIDED WITH HEAT PUMP WIRE CONNECTIONS SHOWN AS AN EXA...

Страница 18: ...o Figures 8 and 9 6 Connect the ground wire to the ground lug provided in the electrical compartment 7 Replace the cover of the junction box 8 Replace the service access panel and replace the screws t...

Страница 19: ...the Remote options When you reach HI LO COM press the MENU button to select the remote Press POOL or SPA to exit the Service Setup mode 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 4 5 2 1 Co...

Страница 20: ...ed up on the red terminal bar with the four 4 wires coming from the indoor controller NOTE If you need to install more than two 2 wires in each terminal order a Zodiac Multiplex PCB Kit 1 2 3 4 RED BL...

Страница 21: ...e inspeccione el equipo y reemplace cualquier parte del sistema de control que haya estado debajo del agua CAUTION Keep all objects off the top of the heat pump Blocking air flow could damage the unit...

Страница 22: ...er a 5 minute delay the control will start the heat pump and the associated right LED will light RED 5 2 5 Spa Mode Optional Maintain Heat If connected the Maintain Heat mode allows the heat pump to m...

Страница 23: ...r Down button to display SELECT USER SETUP LANGUAGE Press the MENU button The SELECT LANGUAGE ENGLISH default language appears use the Up or Down button to scroll through the language options When you...

Страница 24: ...o unit or if the heat pump does not shut off when the filter pump is off Occasionally unusual plumbing configurations or necessary restrictions in the plumbing may cause pressure sensing problems In t...

Страница 25: ...ment It is recommended to change the spa water every 60 days for light usage and every 30 days if usage is heavy 6 2 Winterizing CAUTION Failure to winterize could cause damage to the heat pump and wi...

Страница 26: ...conditions The following basic guidelines are suggested for your inspection 1 Keep the top and surrounding areas of the heat pump clear of all debris 2 Keep all plants and shrubs trimmed and away from...

Страница 27: ...gerant used in the AE Ti heat pump Therefore R 410A should NEVER be used in any of the AE Ti heat pumps The EPA requires certification to purchase or use R 410A It is recommended that service personne...

Страница 28: ...ot heat call for service Heat pump does not run and control board displays FAULT NO FLOW Verify circulating pump is on and all necessary valves are in the correct positions Verify filter and skimmers...

Страница 29: ...ressure builds too high the high pressure switch will open causing the heat pump to shut off immediately The control will sense this fault condition and shut off the compressor until the switch re clo...

Страница 30: ...lacement Kit 2X7 2500 R0561407 20 Heat Exchanger Replacement Kit 2X8 3000 R0561408 21 Compressor 40K 1 Phase 1500 R0510300 21 Compressor 61K 1 Phase 2000 R0510400 21 Compressor 68K 1 Phase 2500 R05105...

Страница 31: ...ploded View 26 12 11 These pressure switches are installed in the refrigerant line near the compressor R E D W I R E B L U E W I R E Y E L L O W W I R E O R A N G E W I R E 2 32 6 7 9 31 8 5 B 21 18 A...

Страница 32: ...tems Inc 2620 Commerce Way Vista CA 92081 1 800 822 7933 www ZodiacPoolSystems com ZODIAC is a registered trademark of Zodiac International S A S U used under license All trademarks referenced herein...

Отзывы: