4.  Connect the wiring from the pool/spa control 

system to the heat pump remote control terminal 

(See Figure 12b).

5.  Restore power to the heat pump and the pool/spa 

control system.

4.5.2.3  Configure the Control panel

1.  Make sure the control is in the 

oFF

 mode.

2.  To enter the Service Setup mode, press and hold 

the 

Menu

pool

, and 

spa

 buttons for 5 

seconds.

note

  The display will revert back to 

oFF

 after one 

minute since the last key press.

3.  Press the 

up

 or 

down

 button to display 

reMote

. The 

seleCt reMote oFF

 

(default remote) appears, use the 

up

 or 

down

 

button to scroll through the Remote options. When 

you reach 

reMote tstat

, press the 

Menu

 

button to select the remote. Press 

pool

 or 

spa

 

to exit the Service Setup mode.

4.  Press 

spa

. For heating, adjust the setpoint to the 

maximum setting. For chilling, adjust the setpoint 

to the minimum setting.

4.5.3   Four-Wire Connection to aqualink

® 

rs 485 Communication

1.  Confirm the EE-Ti heat pump and AquaLink RS 

software revisions are compatible (see Figure 14).

note

  Only a revision "N", or higher, program chip in 

the RS system will support the EE-Ti heat pump 

interface.

2.  Turn off the power to both the heat pump and 

the RS control and open the RS Power Center 

enclosure and remove the front dead panel.

3.  Remove the two (2) screws holding the bezel in 

place and turn the bezel over to view the circuit 

board on the back.

4.  Locate the programmed chip on the Power Center 

Board. In the center of the chip is the revision 

letter. If the revision letter is "

n

" or higher go to 

step 5. If the revision level is "

MMM

" or lower, 

replace the board or connect as shown in Section 

4.5.2.

5.  Use 22 gauge 4-conductor wire (Zodiac Part No. 

4278) to run between the heat pump and the RS 

control, and match the wire color order.

6.  The wires coming from the EE-Ti heat pump can 

be “doubled up” on the red terminal bar with the 

four (4) wires coming from the indoor controller.

note

  If you need to install more than two (2) wires in 

each terminal, order a Zodiac Multiplex PCB Kit, 

1

2

3

4

RED

BLK

YEL

GRN

®

JANDY AquaLink RS

FILTER PUMP OFF

AIR 79°

06/26/04 MON

6:00 PM

EQUIPMENT ON/OFF

ONETOUCH ON/OFF

MENU / HELP

OR

4-Conductor

Wire

EE-Ti Heat Pump Power Interface

OPTIONAL

4 3 2 1

RED

BLK

YEL

GRN

RS Power 

Center

S1

S2

RESET

SERVICE

TIME OUT

FIL

TE

R P

UM

P

AU

X 1

AU

X 2

AU

X 3

AUX 

4

AU

X 5

AUX 

6

AUX 

7

RS6 & RS8 ONLY

RS8 ONLY

HEATER

SOLAR

POOL MODE

SPA MODE

SPA DRAIN

SPA FILL

AUTO

6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1

4 3 2 1 4 3 2 1

OR

Thu January, 2009  3:03 PM

AquaLink Touch

Home

Menu OneTouch

Help

Back

Status

Photos Power

FILTER

PUMP

SPA

POOL

HEAT

Pool Temp

86º

Air Temp

78º

SPA

HEAT

AUX1

AUX2

AUX3

Other

Devices

On/Off

Figure 14.  ee-ti Heat pump Connection to power  

 

Center

which includes the Multiplex Board (Zodiac Part 

No. 6584). Never put more than two (2) wires 

into each of the pins of the terminal bar.

7.  Check all wiring, then apply power to both the 

heat pump and the RS control system. Operation 

can be verified in either Service or Auto mode. See 

the RS Control System manual for instructions 

about operation.
When the EE-Ti heat pump is first powered and 

there is an RS control connected to the heat pump, the 

display on the heat pump will show 

"JandY reMote 

online pusH Menu to disaBle"

. When the 

EE-Ti heat pump is online with the RS control, all 

functionality of the control on the heat pump is disabled. 

The heat pump functions can be controlled only at the 

RS unit. 

To temporarily use the heat pump controls, press 

the 

Menu

 button. The message 

"JandY reMote 

online pusH Menu to disaBle" 

will disappear 

from the heat pump display.  All functionality has now 

been returned to the control on the heat pump. In this 

mode the RS unit is no longer controlling the heat 

pump. 

To return the functionality to the RS unit, cycle 

(turn off and then turn on) the power to the heat pump, 

or press the 

Menu

 button for 5 seconds to enter the 

User Setup Mode and then enable the Zodiac Remote.  

Содержание Jandy EE-Ti

Страница 1: ...n of R410A refrigerant In the event no such state or local requirement exists the installer or maintainer must be a professional with sufficient experience in pool equipment installation and maintenan...

Страница 2: ......

Страница 3: ...17 4 5 1 1 Install the Remote Pool Off Spa Selector 17 4 5 1 2 Configure the Control Panel 17 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 17 4 5 2 1 Configure the AquaLink RS Control System 1...

Страница 4: ...4 Figure 10 Example of MAINTAIN TEMP Wiring to the Time Clock 15 Figure 11 EE Ti Heat Pump Front View 15 Figure 12a Remote Pool Off Spa Connection 3 Wire Connection 16 Figure 12b AquaLink RS or Remote...

Страница 5: ...in drowning Section 1 General Information 1 1 Introduction This manual provides installation and operation instructions for the Zodiac EE Ti models of heat pumps Read these installation and operation...

Страница 6: ...without sacrificing comfort 1 The American Red Cross recommends a maximum water temperature of 78 F 25 C Use an accurate pool thermometer A difference of 4 F 2 C between 78 F and 82 F 26 C and 28 C w...

Страница 7: ...adhered to Water Pipe Heater Connection Plastic 2 PVC Unions included Flow Rate Maximum Optimum Minimum 125 gpm 475 lpm 60 gpm 230 lpm 30 gpm 114 lpm Note If a flow switch is installed R0509700 do no...

Страница 8: ...PRESSURE ALARM 650 PSI reset to 460 PSI REFRIGERANT LOW PRESSURE ALARM HEATING UNITS 58 PSI reset to 127 PSI REFRIGERANT LOW PRESSURE ALARM REVERSE UNITS 35 PSI reset to 74 PSI LOW WATER FLOW ALARM 3...

Страница 9: ...o public access areas 2 2 2 Clearances The heat pump must be placed to provide clearances on all sides for maintenance and inspection See Table 2 Side of Heat pump Minimum Clearances for Operation Rec...

Страница 10: ...ts of water may run off from a roof into the unit Sharp sloping roofs without gutters will allow massive amounts of rain water mixed with debris from the roof to be forced through the unit A gutter or...

Страница 11: ...rrence 3 2 Water Connections at Heat Pump Shipping plugs have been installed in the water inlet and outlet ports of the heat pump at the factory Before installing any plumbing remove the shipping plug...

Страница 12: ...All plumbing on multiple heat pump installations must be done in parallel see Figures 6 and 7 An equal flow of water to each heat pump is important for optimum operation Note It may be necessary to ad...

Страница 13: ...L OR SPA CHEMICAL FEEDER TO POOL OR SPA CHECK VALVE OR OPTIONAL CHLORINE GENERATION SYSTEM JANDY AQUAPURE SHOWN MANUAL BYPASS VALVE CHEMICAL LOOP VENT FOR INDOOR INSTALLATION ONLY HEATER HEAT PUMP FRO...

Страница 14: ...on and Operation Manual Figure 6 Two 2 Heat Pump Plumbing Layout Figure 7 Four 4 Heat Pump Plumbing Layout Manual Bypass Valve 2 PVC 3 PVC Optional Isolation Valves From Filter To Pool Manual Bypass V...

Страница 15: ...ITE BLANC BLANCO Y YELLOW JAUNE AMARILLO BR BK BL Y W BR 24 BK O O Y 24 W FACTORY INSTALLED 230 VAC FIELD INSTALLED 230 VAC FACTORY 24 VAC HARNESS FACTORY 24 VAC FACTORY OPTIONAL 24 VAC FACTORY OPTION...

Страница 16: ...TIONAL 230 VAC BK BLACK NOIR NEGRO BL BLUE BLEU AZUL BR BROWN MARRON MARRON BR W BROWN WITH WHITE TRACE MARRON AVEC UNE TRACE DE BLANC MARRON Y BLANCO GR GREEN VERT VERDE O ORANGE ORANGE ANARANJADO R...

Страница 17: ...Example of MAINTAIN TEMP Wiring to the Time Clock INTERMATIC MODEL T104 MECHANICAL TIMER NOT PROVIDED WITH HEAT PUMP INTERMATIC MODEL T104 NOT PROVIDED WITH HEAT PUMP WIRE CONNECTIONS SHOWN AS AN EXA...

Страница 18: ...o Figures 8 and 9 6 Connect the ground wire to the ground lug provided in the electrical compartment 7 Replace the cover of the junction box 8 Replace the service access panel and replace the screws t...

Страница 19: ...the Remote options When you reach HI LO COM press the MENU button to select the remote Press POOL or SPA to exit the Service Setup mode 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 4 5 2 1 Co...

Страница 20: ...ed up on the red terminal bar with the four 4 wires coming from the indoor controller NOTE If you need to install more than two 2 wires in each terminal order a Zodiac Multiplex PCB Kit 1 2 3 4 RED BL...

Страница 21: ...e inspeccione el equipo y reemplace cualquier parte del sistema de control que haya estado debajo del agua CAUTION Keep all objects off the top of the heat pump Blocking air flow could damage the unit...

Страница 22: ...er a 5 minute delay the control will start the heat pump and the associated right LED will light RED 5 2 5 Spa Mode Optional Maintain Heat If connected the Maintain Heat mode allows the heat pump to m...

Страница 23: ...r Down button to display SELECT USER SETUP LANGUAGE Press the MENU button The SELECT LANGUAGE ENGLISH default language appears use the Up or Down button to scroll through the language options When you...

Страница 24: ...o unit or if the heat pump does not shut off when the filter pump is off Occasionally unusual plumbing configurations or necessary restrictions in the plumbing may cause pressure sensing problems In t...

Страница 25: ...ment It is recommended to change the spa water every 60 days for light usage and every 30 days if usage is heavy 6 2 Winterizing CAUTION Failure to winterize could cause damage to the heat pump and wi...

Страница 26: ...conditions The following basic guidelines are suggested for your inspection 1 Keep the top and surrounding areas of the heat pump clear of all debris 2 Keep all plants and shrubs trimmed and away from...

Страница 27: ...gerant used in the AE Ti heat pump Therefore R 410A should NEVER be used in any of the AE Ti heat pumps The EPA requires certification to purchase or use R 410A It is recommended that service personne...

Страница 28: ...ot heat call for service Heat pump does not run and control board displays FAULT NO FLOW Verify circulating pump is on and all necessary valves are in the correct positions Verify filter and skimmers...

Страница 29: ...ressure builds too high the high pressure switch will open causing the heat pump to shut off immediately The control will sense this fault condition and shut off the compressor until the switch re clo...

Страница 30: ...lacement Kit 2X7 2500 R0561407 20 Heat Exchanger Replacement Kit 2X8 3000 R0561408 21 Compressor 40K 1 Phase 1500 R0510300 21 Compressor 61K 1 Phase 2000 R0510400 21 Compressor 68K 1 Phase 2500 R05105...

Страница 31: ...ploded View 26 12 11 These pressure switches are installed in the refrigerant line near the compressor R E D W I R E B L U E W I R E Y E L L O W W I R E O R A N G E W I R E 2 32 6 7 9 31 8 5 B 21 18 A...

Страница 32: ...tems Inc 2620 Commerce Way Vista CA 92081 1 800 822 7933 www ZodiacPoolSystems com ZODIAC is a registered trademark of Zodiac International S A S U used under license All trademarks referenced herein...

Отзывы: