background image

Page 16

ENGLISH

  

 

 Zodiac

®

 Jandy

® 

Heat Pumps Model EE-Ti   

|

   Installation and Operation Manual

Figure 12a.  

remote pool-off-spa Connection  

 

 

(3-Wire Connection)

Figure 12b.  

aqualink rs or remote tstat 

 

 

Connection (2-Wire Connection)

4.2 

Main power

Electrical wiring to the heat pump must be in 

accordance with the latest edition of the National 

Electric Code

®

 (NEC), ANSI/National Fire Protection 

Association (NFPA) 70 in the United States, and in 

Canada, the Canadian Electrical

®

 Code (CEC) C22.1, 

unless local code requirements indicate otherwise. 

The heat pumps come factory-wired intended for 

use with either 230 VAC, 60 Hz single phase or 3 phase 

field electrical supply depending on the model. See the 

rating plate for the electrical specifications. All wiring 

must be done by a certified electrician.

The following is the procedure to wire the EE-Ti 

to the electrical source specified on the Rating Plate:
1.  Be sure the power to the circuit for the heat pump 

is turned off.

2.   Remove the four (4) screws that attach the service/

access panel to the heat pump unit (see Figure 11). 

3.  Remove the front cover of the sheet metal junction 

box.

4.  Electrical supply lines must be run through 

watertight conduit. Run the wires and conduit from 

the power source and connect them to the conduit 

connection labeled “High Voltage Connection” on 

the right side of the heat pump. See Figure 11 for 

connection location.

5.  Connect the wires to the terminals on the main 

contactor as shown in the wiring diagrams. Refer 

to Figures 8 and 9.

6.  Connect the ground wire to the ground lug 

provided in the electrical compartment.

7.  Replace the cover of the junction box.
8.  Replace the service access panel and replace the 

screws to hold it in place.

9.  Connect a copper bonding wire (8 AWG). (In 

Canada, it shall be not smaller than 6 AWG (13.3 

mm

2

) to the bonding lug on the right side of the 

heat pump.

4.3 

Bonding

  preCauCiÓn

Esta bomba de calor deberá estar conectado a 

una rejilla de unión con hilo de cobre sólido, de 

un diámetro no inferior a 8 AWG. En Canadá, 

no será más pequeño de 6 AWG (13.3 mm

2

).

  Caution

This heater must be connected to a bonding 

grid with a solid copper wire not smaller in 

diameter than 8 AWG (In Canada, it shall be no 

smaller than 6 AWG.)

  attention

L’appareil de chauffage doit être connecté à une 

grille de mise à la terre par un fil de cuivre d’un 

diamètre de calibre minimal 8. Au Canada, cela ne 

devrait pas être inférieur à 6 AWG (13.3 mm

2

).

The National Electrical Code and most other U.S. 

codes require that all metallic components of a pool 

structure, including reinforcing steel, metal fittings, 

and above ground equipment be bonded together with 

a solid copper conductor not smaller than 8 AWG. The 

heat pump, along with pumps and other pool equipment 

must be connected to this bonding grid. A bonding lug 

is provided on the right hand side of the heat pump to 

ensure this requirement is met.

4.4 

pump Connection (Maintain temp 

Feature)

This feature allows the heat pump to turn on the 

pool pump, bypassing the time clock setting, to maintain 

the desired temperature. In order for the 

Maintain 

teMp

 feature to be functional, a dedicated line from 

the pool pump time clock to the Maintain Temp (Pump) 

Содержание Jandy EE-Ti

Страница 1: ...n of R410A refrigerant In the event no such state or local requirement exists the installer or maintainer must be a professional with sufficient experience in pool equipment installation and maintenan...

Страница 2: ......

Страница 3: ...17 4 5 1 1 Install the Remote Pool Off Spa Selector 17 4 5 1 2 Configure the Control Panel 17 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 17 4 5 2 1 Configure the AquaLink RS Control System 1...

Страница 4: ...4 Figure 10 Example of MAINTAIN TEMP Wiring to the Time Clock 15 Figure 11 EE Ti Heat Pump Front View 15 Figure 12a Remote Pool Off Spa Connection 3 Wire Connection 16 Figure 12b AquaLink RS or Remote...

Страница 5: ...in drowning Section 1 General Information 1 1 Introduction This manual provides installation and operation instructions for the Zodiac EE Ti models of heat pumps Read these installation and operation...

Страница 6: ...without sacrificing comfort 1 The American Red Cross recommends a maximum water temperature of 78 F 25 C Use an accurate pool thermometer A difference of 4 F 2 C between 78 F and 82 F 26 C and 28 C w...

Страница 7: ...adhered to Water Pipe Heater Connection Plastic 2 PVC Unions included Flow Rate Maximum Optimum Minimum 125 gpm 475 lpm 60 gpm 230 lpm 30 gpm 114 lpm Note If a flow switch is installed R0509700 do no...

Страница 8: ...PRESSURE ALARM 650 PSI reset to 460 PSI REFRIGERANT LOW PRESSURE ALARM HEATING UNITS 58 PSI reset to 127 PSI REFRIGERANT LOW PRESSURE ALARM REVERSE UNITS 35 PSI reset to 74 PSI LOW WATER FLOW ALARM 3...

Страница 9: ...o public access areas 2 2 2 Clearances The heat pump must be placed to provide clearances on all sides for maintenance and inspection See Table 2 Side of Heat pump Minimum Clearances for Operation Rec...

Страница 10: ...ts of water may run off from a roof into the unit Sharp sloping roofs without gutters will allow massive amounts of rain water mixed with debris from the roof to be forced through the unit A gutter or...

Страница 11: ...rrence 3 2 Water Connections at Heat Pump Shipping plugs have been installed in the water inlet and outlet ports of the heat pump at the factory Before installing any plumbing remove the shipping plug...

Страница 12: ...All plumbing on multiple heat pump installations must be done in parallel see Figures 6 and 7 An equal flow of water to each heat pump is important for optimum operation Note It may be necessary to ad...

Страница 13: ...L OR SPA CHEMICAL FEEDER TO POOL OR SPA CHECK VALVE OR OPTIONAL CHLORINE GENERATION SYSTEM JANDY AQUAPURE SHOWN MANUAL BYPASS VALVE CHEMICAL LOOP VENT FOR INDOOR INSTALLATION ONLY HEATER HEAT PUMP FRO...

Страница 14: ...on and Operation Manual Figure 6 Two 2 Heat Pump Plumbing Layout Figure 7 Four 4 Heat Pump Plumbing Layout Manual Bypass Valve 2 PVC 3 PVC Optional Isolation Valves From Filter To Pool Manual Bypass V...

Страница 15: ...ITE BLANC BLANCO Y YELLOW JAUNE AMARILLO BR BK BL Y W BR 24 BK O O Y 24 W FACTORY INSTALLED 230 VAC FIELD INSTALLED 230 VAC FACTORY 24 VAC HARNESS FACTORY 24 VAC FACTORY OPTIONAL 24 VAC FACTORY OPTION...

Страница 16: ...TIONAL 230 VAC BK BLACK NOIR NEGRO BL BLUE BLEU AZUL BR BROWN MARRON MARRON BR W BROWN WITH WHITE TRACE MARRON AVEC UNE TRACE DE BLANC MARRON Y BLANCO GR GREEN VERT VERDE O ORANGE ORANGE ANARANJADO R...

Страница 17: ...Example of MAINTAIN TEMP Wiring to the Time Clock INTERMATIC MODEL T104 MECHANICAL TIMER NOT PROVIDED WITH HEAT PUMP INTERMATIC MODEL T104 NOT PROVIDED WITH HEAT PUMP WIRE CONNECTIONS SHOWN AS AN EXA...

Страница 18: ...o Figures 8 and 9 6 Connect the ground wire to the ground lug provided in the electrical compartment 7 Replace the cover of the junction box 8 Replace the service access panel and replace the screws t...

Страница 19: ...the Remote options When you reach HI LO COM press the MENU button to select the remote Press POOL or SPA to exit the Service Setup mode 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 4 5 2 1 Co...

Страница 20: ...ed up on the red terminal bar with the four 4 wires coming from the indoor controller NOTE If you need to install more than two 2 wires in each terminal order a Zodiac Multiplex PCB Kit 1 2 3 4 RED BL...

Страница 21: ...e inspeccione el equipo y reemplace cualquier parte del sistema de control que haya estado debajo del agua CAUTION Keep all objects off the top of the heat pump Blocking air flow could damage the unit...

Страница 22: ...er a 5 minute delay the control will start the heat pump and the associated right LED will light RED 5 2 5 Spa Mode Optional Maintain Heat If connected the Maintain Heat mode allows the heat pump to m...

Страница 23: ...r Down button to display SELECT USER SETUP LANGUAGE Press the MENU button The SELECT LANGUAGE ENGLISH default language appears use the Up or Down button to scroll through the language options When you...

Страница 24: ...o unit or if the heat pump does not shut off when the filter pump is off Occasionally unusual plumbing configurations or necessary restrictions in the plumbing may cause pressure sensing problems In t...

Страница 25: ...ment It is recommended to change the spa water every 60 days for light usage and every 30 days if usage is heavy 6 2 Winterizing CAUTION Failure to winterize could cause damage to the heat pump and wi...

Страница 26: ...conditions The following basic guidelines are suggested for your inspection 1 Keep the top and surrounding areas of the heat pump clear of all debris 2 Keep all plants and shrubs trimmed and away from...

Страница 27: ...gerant used in the AE Ti heat pump Therefore R 410A should NEVER be used in any of the AE Ti heat pumps The EPA requires certification to purchase or use R 410A It is recommended that service personne...

Страница 28: ...ot heat call for service Heat pump does not run and control board displays FAULT NO FLOW Verify circulating pump is on and all necessary valves are in the correct positions Verify filter and skimmers...

Страница 29: ...ressure builds too high the high pressure switch will open causing the heat pump to shut off immediately The control will sense this fault condition and shut off the compressor until the switch re clo...

Страница 30: ...lacement Kit 2X7 2500 R0561407 20 Heat Exchanger Replacement Kit 2X8 3000 R0561408 21 Compressor 40K 1 Phase 1500 R0510300 21 Compressor 61K 1 Phase 2000 R0510400 21 Compressor 68K 1 Phase 2500 R05105...

Страница 31: ...ploded View 26 12 11 These pressure switches are installed in the refrigerant line near the compressor R E D W I R E B L U E W I R E Y E L L O W W I R E O R A N G E W I R E 2 32 6 7 9 31 8 5 B 21 18 A...

Страница 32: ...tems Inc 2620 Commerce Way Vista CA 92081 1 800 822 7933 www ZodiacPoolSystems com ZODIAC is a registered trademark of Zodiac International S A S U used under license All trademarks referenced herein...

Отзывы: