Page 24

ENGLISH

  

 

 Zodiac

®

 Jandy

® 

Heat Pumps Model EE-Ti   

|

   Installation and Operation Manual

4.  Cover only the top of the heat pump to prevent 

debris from falling into the unit. Do not wrap the 

sides of the heat pump with any plastic or other 

material that will retain heat or moisture inside the 

unit.

6.3 

spring start-up

If your heat pump has been winterized, perform 

the following steps when starting the system in the 

Spring: 

1.  Uncover the heat pump and inspect the top and 

sides for any debris or structural problems.

2.  Connect the water inlet and outlet unions located 

on the lower front panel of the heat pump.

3.  Turn on the filter pump to supply water to the 

heat pump. Circulate water through the system 

long enough to cycle all of the pool water through 

the filter. Check for leaks in and around the heat 

pump. 

4.  Check the pool chemistry and balance as 

necessary.

5.  Turn on the electrical power to the heat pump at 

the main breaker panel.

6.4 

inspection and service

Zodiac heat pumps are designed and constructed 

to provide long performance life when installed and 

operated properly under normal conditions. Periodic 

inspections are important to keep your heat pump 

running safely and efficiently through the years. 

6.4.1  owner inspection

  Caution

Do not use this heat pump if any part has been 

under water. Immediately call a qualified service 

technician to inspect the heater and replace any 

part of the control system which has been under 

water.

  

attention

N’utilisez pas cet appareil s’il a été plongé dans 

l’eau, même partiellement. Faites inspecter 

l’appareil par un technicien qualifié et remplacez 

toute partie du système de contrôle et toute 

commande qui ont été plongés dans l’eau

  preCauCiÓn

No utilice esta bomba de calor si algunos de 

sus componentes han estado debajo del agua. 

Póngase inmediatamente en contacto con un 

técnico de mantenimiento cualificado para que 

inspeccione el equipo y reemplace cualquier 

parte del sistema de control que haya estado 

debajo del agua.

Zodiac recommends that you inspect your heat 

pump on a regular basis and especially after abnormal 

weather conditions. The following basic guidelines are 

suggested for your inspection:

1.  Keep the top and surrounding areas of the heat 

pump clear of all debris.

2.  Keep all plants and shrubs trimmed and away from 

the heat pump.
The heat pump will produce condensation (water) 

while in operation. The heat pump base is designed to 

allow the condensation to exit through the bottom drain 

port when the unit is running. The condensation will 

increase as the outdoor air humidity level increases. 

Check the following at regular intervals to ensure proper 

condensate drainage:
1.  Visually inspect and clear the bottom drain ports 

of any debris that could clog the ports.

2.  Ensure that condensate water does not puddle 

inside the heat pump 

3.  Ensure that condensate run-off is properly directed 

away from the equipment pad to keep it from 

undermining the pad.
During normal operation, the heat pump produces 

3 to 5 gallons of condensate per hour. If condensate 

drainage is above this range during operation or if water 

continues to drain from the base when the heat pump 

is not in operation for more than an hour, a leak in the 

internal plumbing may have occurred. Call a qualified 

heat pump technician to investigate the problem.

Keep the top air flow discharge and air flow intake 

area clear of debris so the air flow though the heat pump 

is not restricted. The cooler discharge air from the top 

should not accumulate and be drawn into the side air 

intake coils. Keep all plants and shrubs trimmed away 

from the heat pump. 

Make sure the front of the unit is accessible for 

future service.

Keep lawn sprinkler heads from spraying on the 

heat pump to prevent corrosion and damage. Use a 

deflector if needed.

If the unit is installed under a very sharp roof pitch 

or under a roof without a gutter, a gutter or diverter 

should be fitted to prevent excessive water from pouring 

down into the unit.

6.4.2  professional inspection

Inspections performed at least once a year by a 

qualified technician are required to maintain your heat 

pump’s safe and efficient operation. The following basic 

safety checks must be performed.

Check for loose or broken wires and terminal 

connections.

2.  Verify the pressure switch or flow switch 

operation. Turn the heat pump OFF.  Disconnect 

the power to the pump time clock, or turn the 

Содержание Jandy EE-Ti

Страница 1: ...n of R410A refrigerant In the event no such state or local requirement exists the installer or maintainer must be a professional with sufficient experience in pool equipment installation and maintenan...

Страница 2: ......

Страница 3: ...17 4 5 1 1 Install the Remote Pool Off Spa Selector 17 4 5 1 2 Configure the Control Panel 17 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 17 4 5 2 1 Configure the AquaLink RS Control System 1...

Страница 4: ...4 Figure 10 Example of MAINTAIN TEMP Wiring to the Time Clock 15 Figure 11 EE Ti Heat Pump Front View 15 Figure 12a Remote Pool Off Spa Connection 3 Wire Connection 16 Figure 12b AquaLink RS or Remote...

Страница 5: ...in drowning Section 1 General Information 1 1 Introduction This manual provides installation and operation instructions for the Zodiac EE Ti models of heat pumps Read these installation and operation...

Страница 6: ...without sacrificing comfort 1 The American Red Cross recommends a maximum water temperature of 78 F 25 C Use an accurate pool thermometer A difference of 4 F 2 C between 78 F and 82 F 26 C and 28 C w...

Страница 7: ...adhered to Water Pipe Heater Connection Plastic 2 PVC Unions included Flow Rate Maximum Optimum Minimum 125 gpm 475 lpm 60 gpm 230 lpm 30 gpm 114 lpm Note If a flow switch is installed R0509700 do no...

Страница 8: ...PRESSURE ALARM 650 PSI reset to 460 PSI REFRIGERANT LOW PRESSURE ALARM HEATING UNITS 58 PSI reset to 127 PSI REFRIGERANT LOW PRESSURE ALARM REVERSE UNITS 35 PSI reset to 74 PSI LOW WATER FLOW ALARM 3...

Страница 9: ...o public access areas 2 2 2 Clearances The heat pump must be placed to provide clearances on all sides for maintenance and inspection See Table 2 Side of Heat pump Minimum Clearances for Operation Rec...

Страница 10: ...ts of water may run off from a roof into the unit Sharp sloping roofs without gutters will allow massive amounts of rain water mixed with debris from the roof to be forced through the unit A gutter or...

Страница 11: ...rrence 3 2 Water Connections at Heat Pump Shipping plugs have been installed in the water inlet and outlet ports of the heat pump at the factory Before installing any plumbing remove the shipping plug...

Страница 12: ...All plumbing on multiple heat pump installations must be done in parallel see Figures 6 and 7 An equal flow of water to each heat pump is important for optimum operation Note It may be necessary to ad...

Страница 13: ...L OR SPA CHEMICAL FEEDER TO POOL OR SPA CHECK VALVE OR OPTIONAL CHLORINE GENERATION SYSTEM JANDY AQUAPURE SHOWN MANUAL BYPASS VALVE CHEMICAL LOOP VENT FOR INDOOR INSTALLATION ONLY HEATER HEAT PUMP FRO...

Страница 14: ...on and Operation Manual Figure 6 Two 2 Heat Pump Plumbing Layout Figure 7 Four 4 Heat Pump Plumbing Layout Manual Bypass Valve 2 PVC 3 PVC Optional Isolation Valves From Filter To Pool Manual Bypass V...

Страница 15: ...ITE BLANC BLANCO Y YELLOW JAUNE AMARILLO BR BK BL Y W BR 24 BK O O Y 24 W FACTORY INSTALLED 230 VAC FIELD INSTALLED 230 VAC FACTORY 24 VAC HARNESS FACTORY 24 VAC FACTORY OPTIONAL 24 VAC FACTORY OPTION...

Страница 16: ...TIONAL 230 VAC BK BLACK NOIR NEGRO BL BLUE BLEU AZUL BR BROWN MARRON MARRON BR W BROWN WITH WHITE TRACE MARRON AVEC UNE TRACE DE BLANC MARRON Y BLANCO GR GREEN VERT VERDE O ORANGE ORANGE ANARANJADO R...

Страница 17: ...Example of MAINTAIN TEMP Wiring to the Time Clock INTERMATIC MODEL T104 MECHANICAL TIMER NOT PROVIDED WITH HEAT PUMP INTERMATIC MODEL T104 NOT PROVIDED WITH HEAT PUMP WIRE CONNECTIONS SHOWN AS AN EXA...

Страница 18: ...o Figures 8 and 9 6 Connect the ground wire to the ground lug provided in the electrical compartment 7 Replace the cover of the junction box 8 Replace the service access panel and replace the screws t...

Страница 19: ...the Remote options When you reach HI LO COM press the MENU button to select the remote Press POOL or SPA to exit the Service Setup mode 4 5 2 Two Wire Connection to an AquaLink RS or TSTAT 4 5 2 1 Co...

Страница 20: ...ed up on the red terminal bar with the four 4 wires coming from the indoor controller NOTE If you need to install more than two 2 wires in each terminal order a Zodiac Multiplex PCB Kit 1 2 3 4 RED BL...

Страница 21: ...e inspeccione el equipo y reemplace cualquier parte del sistema de control que haya estado debajo del agua CAUTION Keep all objects off the top of the heat pump Blocking air flow could damage the unit...

Страница 22: ...er a 5 minute delay the control will start the heat pump and the associated right LED will light RED 5 2 5 Spa Mode Optional Maintain Heat If connected the Maintain Heat mode allows the heat pump to m...

Страница 23: ...r Down button to display SELECT USER SETUP LANGUAGE Press the MENU button The SELECT LANGUAGE ENGLISH default language appears use the Up or Down button to scroll through the language options When you...

Страница 24: ...o unit or if the heat pump does not shut off when the filter pump is off Occasionally unusual plumbing configurations or necessary restrictions in the plumbing may cause pressure sensing problems In t...

Страница 25: ...ment It is recommended to change the spa water every 60 days for light usage and every 30 days if usage is heavy 6 2 Winterizing CAUTION Failure to winterize could cause damage to the heat pump and wi...

Страница 26: ...conditions The following basic guidelines are suggested for your inspection 1 Keep the top and surrounding areas of the heat pump clear of all debris 2 Keep all plants and shrubs trimmed and away from...

Страница 27: ...gerant used in the AE Ti heat pump Therefore R 410A should NEVER be used in any of the AE Ti heat pumps The EPA requires certification to purchase or use R 410A It is recommended that service personne...

Страница 28: ...ot heat call for service Heat pump does not run and control board displays FAULT NO FLOW Verify circulating pump is on and all necessary valves are in the correct positions Verify filter and skimmers...

Страница 29: ...ressure builds too high the high pressure switch will open causing the heat pump to shut off immediately The control will sense this fault condition and shut off the compressor until the switch re clo...

Страница 30: ...lacement Kit 2X7 2500 R0561407 20 Heat Exchanger Replacement Kit 2X8 3000 R0561408 21 Compressor 40K 1 Phase 1500 R0510300 21 Compressor 61K 1 Phase 2000 R0510400 21 Compressor 68K 1 Phase 2500 R05105...

Страница 31: ...ploded View 26 12 11 These pressure switches are installed in the refrigerant line near the compressor R E D W I R E B L U E W I R E Y E L L O W W I R E O R A N G E W I R E 2 32 6 7 9 31 8 5 B 21 18 A...

Страница 32: ...tems Inc 2620 Commerce Way Vista CA 92081 1 800 822 7933 www ZodiacPoolSystems com ZODIAC is a registered trademark of Zodiac International S A S U used under license All trademarks referenced herein...

Отзывы: