background image

 

STW164IP 

12660-0710-00

 

Page

 

23 / 30 

www.ziehl.de 

  

10.6.9  Simulation  

On the device, Menu 
/ Simulation 

In the Web Browser, 
Register Home / Button 
Simulation 

Parameter, description 

STW16xM (Address 
0.....31) 

on / off

 

Machines (Address 0.....31) 

on / off

 

Simulated switching on/off of the machines 

Not possible.

 

Reset addition time 

A cleaning is started at the next possible time 

Not possible.

 

Relay simulation 

Switch relays K3 and K4 on/off manually 

No errors are logged during a simulation on the device / via the website. 
 

10.6.10 

Info 

On the device, Menu 
/ Info 

In the web browser, 
Register System 

Parameter, description 

Firmware 

Firmware version 

Firmware version on the device 

Not possible.

 

Bootloader version 

Bootloader version on the device 

Not possible.

 

Hardware version 

Hardware version of the device 

Serial number 

Serial number 

Device serial number 

Not possible.

 

Item number 

Item number of the device 

Not possible.

 

Last modified by 

Documentation of who and when the last change 

Not possible.

 

Last modified on 

was made to the device 

 

On the device, 
Menu / Info 

In the web browser, 
Register Counter 

Parameter, description 

Operating hours 

Counter STW164IP and 
Counter 
STW161M / STW168M 

Operating hours of devices controlled by the STW164IP. 
The values can be reset via the web interface 

Slide Counter 

Counter 
STW161M / STW168M 

Number of slider openings. The values can be reset via 
the web interface 

 
 

10.7  Code lock / code reset 

The device can be protected against unauthorized changes to 

the device 

(via joystick button) with the code 

lock (see Parameter -> Settings -> Code lock). 
A pin code is used for this purpose (factory setting: 504). 

Reset pin code/switch off code lock, on the device: 

• 

Interrupt supply voltage 

• 

Press (and hold) the joystick button upwards 

• 

Switch on the supply voltage (keep pressing the joystick button) 

• 

After approx. 4 seconds, the reset menu appears, select code lock and press the button to the right 

• 

Code lock is switched off, pin code = 504 

Via web interface: 

• 

In the System menu: Switch off the code lock and apply with the "Save" button 

 

10.8  Simulation 

With the simulation on the device (see Parameters -> Simulation), the machines on the STW161M / STW168M 
can be switched on and off in a simulated manner. 

The state of the sliders is displayed (state description, see 

display pages 

under Point 

7

). 

 

 

 

Содержание STW164IP

Страница 1: ...Operating Manual STW164IP updated 2023 12 05 dr from Firmware 0 00 For more information and help about this product please scan the QR Code or choose the following link STW164IP Operating manual Quick...

Страница 2: ...e 12 7 3 Discharge 12 7 3 1 Starts with extraction 12 7 3 2 Starts with cleaning 12 7 4 Input Y1 I0 I31 12 7 5 Input Y2 13 7 6 Relays K3 and K4 13 7 7 Analog output 13 8 Important Information 13 9 Ass...

Страница 3: ...6 Disposal 30 1 General Notes Compliance with the following instructions is mandatory to ensure the functionality and safety of the product If the following instructions given especially but not limit...

Страница 4: ...e table can be used by the customer to document the set values of the parameters enter values in tables Menu on the device Machines Parameters on website Configuration Machines Default value My data a...

Страница 5: ...flow line 1 10 Min Vol line 2 Min volume flow line 2 10 Min Vol line 3 Min volume flow line 3 10 Min Vol line 4 Min volume flow line 4 10 Open more Open more sliders Yes Cleaning Configuration Cleanin...

Страница 6: ...ditional sliders can be opened to optimize the air flow Assignment to different lines and prioritization is possible It is also possible to control cleaning and discharge The parameters are convenient...

Страница 7: ...ther sliders can be prevented o Message if exceeded Minimum volume flow of the entire extraction 1 100 o If necessary automatic opening of additional sliders o Sequence adjustable via priority of the...

Страница 8: ...ates Modbus TCP read Display and operation Color LCD display for displaying the operating conditions and for programming Intuitive operations via joystick Convenient display of operating states and pr...

Страница 9: ...beginning or end of the BUS line the terminating resistors must be switched on at the corresponding STW168M or STW161M beginning and end of the BUS line 6 1 Connection of additional power supplies It...

Страница 10: ...machine is switched on After delay time for machine The slider flap of the extraction channel opens After delay time for extraction Switches on the extraction system Machine I limit value exceeded Mac...

Страница 11: ...age is displayed on the device and in the web browser This message can be parameterized to a relay Extraction max vol Extraction open more Relay volume flow Min volume flow line 1 4 Smallest volume fl...

Страница 12: ...hes on and at least 50 of the continuous shaking time has not yet elapsed cleaning is restarted at the next opportunity 7 3 Discharge Two different discharge modes are available 7 3 1 Starts with extr...

Страница 13: ...output Proportional to the volume flow a voltage is output at the analogue output This can control a frequency converter on an extraction motor Output voltage DC 0 10 V at 0 volume flow Analog output...

Страница 14: ...to the BUS lines 9 Assembly The device can be fastened Distributor installation on 35mm mounting rail to EN 60715 With M4 screws for wall mounting additional bars not included Connect according to the...

Страница 15: ...e operation The device is operated via the integrated joystick button It can be operated in four directions up down left and right In conjunction with the graphical colour display operation of the dev...

Страница 16: ...resses of STW161M STW168M connected to the RS485 BUS Display of the current consumption of the individual machines measured bySTWA1 H converters When switches are used machine on off is displayed Meas...

Страница 17: ...u Press for 2s Press back to the display pages Press Down press Up press Submenu Call up submenu Exit submenu Call up parameter menu Navigate within the submenu From the main menu select the submenu a...

Страница 18: ...integrated Up to four lines are supported Priority Adr 0 31 1 32 Priority Adr 0 31 1 32 Priority in which order additional sliders open to reach the minimum volume flow 1 highest In each line the pri...

Страница 19: ...m volume flow of the entire system To achieve this additional valves flaps are opened if necessary Max Vol 5 100 Max volume flow 5 100 Maximum permissible volume flow of the entire system If exceeded...

Страница 20: ...ning time K2 off during the vibration intervals Continuous vibration time 00 00 20 00 mm ss Continuous vibration time 0 1200s The continuous vibration time starts after the vibration intervals Static...

Страница 21: ...eterize to a relay End position of slider open not reached within the parameterized time Fault off Relay K3 Relay K4 Fault off Rel K4 Rel K3 Reporting faults errors Error from RS485 BUS device not rea...

Страница 22: ...of the DNS server on the network Not possible Time server settings and Time zone settings Settings for date time for error memory In the event of operation without a time server the date time will not...

Страница 23: ...nfo In the web browser Register Counter Parameter description Operating hours Counter STW164IP and Counter STW161M STW168M Operating hours of devices controlled by the STW164IP The values can be reset...

Страница 24: ...rameters Display settings for LCD display see Parameters Code lock see Parameters Firmware update STW164IP o Update notification message when update is available o Firmware status if necessary the fir...

Страница 25: ...gged Storage in case of occurrence of a new error Storage in case of disappearance of an error Storage of o Status of all max possible STW161M STW168M on the BUS o Relay state K1 K4 o Status inputs Y1...

Страница 26: ...server but after 20 s at the latest 11 7 Register Counter STW164IP Operating hours counter STW164IP Switch on times of relay extraction cleaning K3 and K4 values can be reset STW161M STW168M Address 0...

Страница 27: ...nd position contact on the corresponding STW161M If necessary adjust parameters machine end position Y4 extend time Display website reports STW16xM 24V On display page 2 3 the measured value of the ST...

Страница 28: ...A Ue 24V DC 13 Ie 0 2A Ue 250VV Test conditions for relay outputs EN 61010 1 Rated impulse withstand voltage Overvoltage category Degree of contamination Rated insulation voltage Ui 4000V III 2 300V I...

Страница 29: ...61326 1 industrial environment Installation conditions Permissible ambient temperature Permissible storage temperature Installation height Climate resistance Permissible wiring temperature Oscillation...

Страница 30: ...30 www ziehl de 15 Design V8 16 Disposal Disposal should be carried out properly and in an environmentally friendly manner in accordance with legal provisions ZIEHL is registered with the EAR Foundati...

Отзывы: