STW164IP
12660-0710-00
Page
25 / 30
www.ziehl.de
11.4 Register - Network
•
network settings
•
Modbus settings (Modbus TCP protocol on port 502)
•
Time server settings and time zone settings (for current time in the device, important to be able to
evaluate error memory in the device)
11.5 Register - User
•
User management (providing device with read and write permissions for users on the network)
•
User (activate user and create name and password)
o
User name for guest when logging in (fixed, cannot be changed): "guest", "Guest" or leave blank
•
User permissions (determine which users have which rights on which pages)
Attention: Changes (including to passwords) are only applied after saving (Save button)
11.6 Register - Logging
Error memory (occurring errors are logged)
•
Storage in case of occurrence of a new error
•
Storage in case of disappearance of an error
•
Storage of
o
Status of all max. possible STW161M/ STW168M on the BUS
o
Relay state K1.....K4
o
Status inputs Y1 and Y2
o
Voltage at analog output OUT
o
Error status
Description Error Log...
machine 1...31:
bit-0 (valence
= 1): Module is switched on in configuration of STW164IP
bit-1 (valence
= 2): Communication to STW161M / STW168M available
bit-2 (valence
= 4): Relay on STW161M / STW168M has energized
bit-3 (valence
= 8): Status of Y3 on STW161M or Ix on STW168M (limit value exceeded, or
contact closed)
bit-4 (valence = 16): Status of Y4 on STW161M (contact for end position closed)
bit-5 (valence = 32): Error on supply voltage of STW161M / STW168M
(Voltage too high / too low)
Relays:
bit-0: Relay K1 energized
bit-1: Relay K2 energized
bit-2: Relay K3 energized
bit-3: Relay K4 energized
in Y1+Y2:
bit-0: Input Y1 closed
bit-1: Input Y2 closed
Analog out:
Voltage at analogue output in mV