STW164IP
12660-0710-00
Page
16 / 30
www.ziehl.de
Display page 1
Display page 2
Display page 3
Time bar, orange (K1 only):
Bar increasing: Switch-on delay elapses (K1 still off)
Bar decreasing: Overrun time elapses (K1 still energized)
Bar static on: Extraction on (K1 energized)
Relay display K1...K4:
yellow = tightened, white = dropped
Display of operating states,
Extraction K1:
State of extraction, on/off
Slider open:
Number of open sliders in the extraction channels
Vol. flow:
Volume flow of the extraction system
t-addition time: Current addition time, at 0s -> filter cleaning is pending
Discharge: State of discharge, on/off
BUS error: General error display, will be displayed if necessary (here: BUS error)
Y2: Displayed when input Y2 has been enabled (closed)
Number of the display page, with more than 16 parameterized sliders/flaps there are 4 pages
Addresses of STW161M/STW168M connected to the RS485 BUS
Display of the current consumption of the individual machines (measured bySTWA1 (H)
converters). When switches are used, machine "on/off" is displayed
•
Measured value red:
Error in communication with corresponding
STW161M/STW168M
•
Measured value highlighted in red: End position error on the slider/flap or error in the supply
Status of the extraction sliders/flaps on the machines
•
Bar off:
Slider/flap closed
•
Bar green:
- Slider/flap open
- Bar increasing: Switch-on delay elapses (slider still closed)
Bar decreasing: Overrun time elapses (slider still open)
•
Bar white:
- Slider/flap open so that minimum volume flow is reached
•
Bar cyan:
Bar decreasing: Time of "Last overrun" elapses (slider still open)
Display of various information
•
Firmware:
Firmware version on the device
•
Input Y1:
0 = open, 1 = closed
•
Input Y2:
0 = open, 1 = closed
•
U Out:
Voltage at output OUT (terminals O+/O-)
•
Code lock:
Code lock against unauthorized adjustment on the device = off /
on
•
IP address:
IP address of the device in the Ethernet network