Installation and Operating Instructions V01
55
Type
TLC8000
TLC10000
Rated output power
8000 W
10000 W
Max. output active power
(1)
8800 W
10000 W
Max. output apparent power
8800 VA
10000 VA
Rated AC voltage
3/N/PE, 220/380V, 230/400V,240/415V
Rated AC voltage range (line to line)
(2)
277 V to 512 V
Rated power frequence
50 Hz
AC power frequency
(3)
50 Hz/ 60 Hz
Operating range at AC power frequency
50 Hz
45 Hz to 55Hz
Operating range at AC power frequency
60 Hz
55 Hz to 65Hz
Rated output current at 220 V
3×12.1 A
3×15.2 A
Rated output current at 230 V
3×11.6 A
3×14.5 A
Rated output current at 240 V
3×11.1 A
3×13.9 A
Max. continuous output current
3×12.1 A
3×15.2 A
Power factor
VDE-AR-N 4105
0.85ind - 0.85cap
Other safety
>0.97 at 20% load, >0.99 at 100% load
Inrush current(peak and duration)
41A@252µs
41A@250µs
Harmonic distortion (THD) at P
ac,r
< 3%
Night-time power loss
<0.6 W
Standby power loss
<12 W
(1)
Maximum 10% AC overload can be activated by settings on LCD (refer to section
9.4.13) , Please make sure that it is compliant with local regulations and DNO’s
requirements before enabling. .
(2) The AC voltage range depends on the local safety standards and rules.
(3) The AC frequency range depends on the local safety standards and rules.