9.4.12 Safety regulations setting
Press the "
▲
" or "
▼
" button to enter the “Setting” item of main menu, choose the
sub-menu “Advanced Setting” and press the "
" button to enter, then a pop-up
window for password appears. Enter the correct password and press the "
"
button to enter the “advanced setting” sub-menu page. Please get the correct
password from the service engineer.
Then select the “Safety Setting” item and press the "
" button to enter the “safety”
page.
Password
Password:0 0 0 0
0
Overload Setting
Active power control
Reactive power control
PV Mode Setting
Advanced Setting
EEG Setting
Safety Setting
At the “safety” page, use the "
▲
" or "
▼
" button to adjust the selected parameter and
confirm with the "
" button, then adjust the next parameters in turn. Parameter
adjustment will be finished after the "
" button has been pressed. Press the "ESC"
button to cancel.
Safety
Standard:
DE VDE-AR-N 4105
OVP2
:
265.5 V
OVP1
:
255.0 V
UVP1
:
185.0 V
UVP2
:
180.0 V
10Min-Mean
:
180.5 V
Safety
OFP2
:
54.50 Hz
OFP1
:
UFP1
:
UFP2
:
53.50 Hz
47.50 Hz
45.50 Hz
There are two pages for safety regulation parameters setup. After adjusting the last
parameter of the first page, the page will automatically jump to the second page.
The safety of the grid may be influenced due to the improper operating
parameters
The default parameters settings comply with the local regulations.
Don’t change the values of the monitored operating limits unless the grid operator
gives his approval.