Zeta Alarm Systems.
Classic 2000 Mk II Operation Manual
Revision 1.0
Part # MAN-Z3K-01
Page 87
NOTES:
1. Required for remote ZACMs
2. SLC Loops are Current Limited at 80mA in alarm. This requirement is included on the last line of the Detectors/
Modules section of this chart.
3. Review the top line for the indication of standby and alarm current
4. Current values are in mAmps unless otherwise specified.
Other - NAC #4, 2.75 Amps Maximum
0
0
0
0
0
GMS24-15/75WR
0
0
139
0
0
GEC24-15/75WR
0
0
142
0
0
TOTAL STANDBY CURRENT - mA
0
TOTAL ALARM CURRENT - mA
0
TOTALS
A) Supervisory (standby) Current - mA (Item 35, above)
0
B) Supervisory Time in Hours (24 or 60)
24
C) Supervisory Requirements (A x B)
0
D) Power Supply Size (Enter .00575 or .0075) or Alarm Current (Item 36, above)
0
E) Alarm Time in Minutes (For 5mins enter .0833; for 10mins enter .167)
0
F) Alarm Requirement (D x E)
0
G) Battery Backup Requirement (C + F)
0
H) 20% Safety Factor (G x .2)
0
I) Battery Requirement w/ 20% Safety Factor (G + H)
0
J) Required Battery Size in Amps.
0
SYSTEM COMPONENTS
Quantity
Stand-By
Current
(mA)
Maximum
Alarm
Current
(mA)
Total
Stand-By
Current
(mA)
Total
Alarm
Current