6.4 Addressing Serial Devices
This section describes the relationship of network addresses to programmable point addresses
and instructions for setting addresses.
Each serial device must have a unique network address. For simplicity, we have established point
address ranges that are fixed to each network address. Point address ranges associated with each
network address are shown in the following table:
Relationship of Network Address to Point Range
6.4.1 ZACM Addressing
Each ZACM, except the ZACM on the CP3 board, contains a position DIP switch for network
addressing purposes. The system fixes the ZACM addresses as follows:
64 =
No Switch
“On board” ZACM
65 =
# 1 On
# 2 Off
66 =
# 1 Off
# 2 On
67 =
# 1 On
# 2 On
*Special order – see Appendix A for part numbers.
Network
Address
ZFZA/ZTZB
Number
ZTZB Point
Addresses
Point Addresses
(ZFZA)
(Empty)
48
1
1 - 10
1 - 5
6 - 10
49
2
11 - 20
11 - 15
16 - 20
50
3
21 - 30
21 - 25
26 - 30
51
4
31 - 40
31 - 35
36 - 40
52
5
41 - 50
41 - 45
46 - 50
53
6
51 - 60
51 - 55
56 - 60
54
7
61 - 70
61 - 65
66 - 70
55
8
71 - 80
71 - 75
76 - 80
56
9
81 - 90
81 - 85
86 - 90
57
10
91 - 100
91 - 95
96 - 100
58
11
101 - 110
101 - 105
106 - 110
59
12
111 - 120
111 - 115
116 - 120
Network
Address
ZACM
Number
Associated
SLC
Point Addresses
(1,3,5,7) AC
(2,4,6,8) BD
64
1
1 & 2
1-126
1-126
65
2
3 & 4
1-126
1-126
66
3
5 & 6
1-126
1-126
67
4
7 & 8
1-126
1-126
68*
5
A & B (10 & 11)
1-126
1-126
69*
6
C & D (12 & 13)
1-126
1-126