Zeta Alarm Systems.
Classic 2000 Mk II Operation Manual
Revision 1.0
Part # MAN-Z3K-01
Page 4
Relay Outputs
Form C relay outputs for System Alarm and Trouble
Up to 20 programmable auxiliary system relays optional from the main board
Cabinet
16-gauge cold rolled steel finished in red powder coat enamel with space at bottom
for batteries
Conduit knockouts in the top, sides, and back
Removable Door with key lock
Will house a 2 or 4 SLC system
Analog Addressable Sensors
Photoelectric and ionization sensor heads have sensitivity set in the software database
Heat sensor is programmable to alarm at 135° F to 190° F
Sensor address is set via DIP switches
Addressable Modules
Modules fit a single gang box or 4" square boxes and have an LED visible through cover
A sounder control module provides a NAC
An input-output module has a supervised input and a relay output that follows its input and
may be configured as input point or output point
The isolator module, while not addressable, includes a mounting base and does not require an
electrical box for mounting
Addresses are set via DIP switches
Module inputs can be wired as Class A or B, which is switch selectable at the module
1.2.2 List of Optional Features
DC Power
A heavy duty 7.5 amp power supply
ZIPB-3 power supply/ booster provides 3 amp distributed power
Auxiliary System Relay Outputs
Up to 4 ZZRM Form C relay modules may be added (20 programmable system relay contacts)
Communication Port Options
Zeta Isolated communication port (ZICP) and non-isolated communication port (ZSCP3)
1.2.3 List of Network Features
All devices below communicate with the panel through an RS-485 data bus.
SLC Expansion
ZACM-A modules with 2 loops of 126 points can be added to the base system to reach 1512
point capacity
Up to 600 Conventional Initiating Zones can be added by using Dual Input / Output Modules
(ZDIO), Panel Network Interface for the Sigma Mk II panel (ZPN1-1K), or five (ZFZA) or ten
(ZTZB) zone modules on the RS-485 data bus
Remote Annunciation
Remote Display Annunciator provides a remote 80-character display to mimic the panel display
ZRLD Modules will drive up to 60 LEDs for graphic annunciators
All annunciators communicate with the panel through an RS-485 data bus