2.2.1 Mount Enclosure
Install the Enclosure as follows:
1. Carefully unpack the system components and inspect for any damage due to shipping.
2. Mount the enclosure in a clean, dry, vibration-free area where extreme temperatures are not
encountered. The location should be readily accessible with sufficient room for easy installa-
tion and maintenance.
3. Locate the top of the cabinet 6 feet above the floor, with the hinge mounting on the left.
4. Mount centering the single hole in the upper back of the cabinet to the center of a wall stud.
After the panel has been properly located using the center-mounting hole, the panel can be
secured using the bottom mounting holes located in each corner. Use screws or bolts no
smaller than No. 10 or 3/16 inches in diameter for cabinet mounting. Always make certain the
panel is securely anchored.
5. Complete
all
conduit
connections to the cabinet. Use the knockouts provided in the top, sides,
or back of the cabinet. Wire should NOT enter the bottom of the cabinet, since this area is
intended for batteries.
NOTE: All wiring should be in accordance with Article 760 of the National Electrical Code NFPA 70
and state and local codes for fire alarm systems. All conductors should be tagged or otherwise
coded and logged at installation to identify circuit assignment, polarity, and Class “A” circuits,
whether outgoing or incoming.
2.2.2 Install CP3 Board
NOTE: All expansion boards should be attached to
the CP3 prior to mounting the CP3 to the Power Chas-
sis and assembling in the cabinet. Never attach any
accessory boards to the CP3 without first removing all
power (AC and batteries). Doing so will VOID the war-
ranty.
(Refer to Figure I-1 to properly identify components.)
After enclosure has been securely attached in the
proper mounting location, attach the CP3 module to
the Power Chassis. This is accomplished by aligning
the seven plated holes on the board with the mounting
studs on the Power Chassis and making sure that the
power connection plug of the CP3 is directly above the
Power Chassis socket. Press down firmly until the
board “snaps” into place.
2.2.3 Mount Chassis in Enclosure
After the enclosure has been securely mounted in a
suitable mounting location, set the mounting studs at
the bottom of the power chassis into the mounting
hinge brackets inside the cabinet. The Power Chassis
will set securely in the brackets, extending like a shelf
to allow connection of AC power. (Refer to Figure I-2
for mounting illustration.)